Cambridge Air Solutions
20
SA-Series Technical Manual
OPERATING INSTRUCTIONS
TSS CONTROLLER
The Cambridge Air Solutions TSS Controller provides several features to tailor the operation of the Cambridge
heating system to particular applications.
• Seven day programmable clock.
• Separate temperature settings for Heating and Setback operation.
• Separate schedules for Summer Ventilation and Heating modes.
• Setback Override for temporary heating operation.
• Real-Time Clock with automatic adjustment for Daylight Saving Time.
• Nine Holiday Setback Periods for temporary setback operation.
• Temperature Calibration for accurate temperature control.
• Capacitor backup maintains current time and day of week for power loss of up to 96 hours.
• EEPROM storage maintains schedules and temperature settings indefinitely.
The thermistor enclosure (SH-1) is packed inside the Remote Control Station for shipment. It can be mounted
on the exterior sides or bottom of the Remote Control Station or a remote location within 500 feet of the Remote
Control Station using 18 gauge stranded, twisted-pair, shielded cable. The thermistor is hard wired to the
temperature sensor terminal block.