34
SA-Series Technical Manual
TROUBLESHOOTING INSTRUCTIONS
TROUBLESHOOTING GUIDE
Problem
Possible Cause
Corrective Action
X. ERRATIC OR
PULSATING FLAME
1. High Pressure Regulator
a) Vent undersized
b) Defective regulator
a) Enlarge vent piping size or reduce vent
piping length
b) Replace regulator
2. Amplifier
a) Hunting
b) Temperature control system out of
calibration
c) Defective amplifier
a) Adjust sensitivity control dial counter-
clockwise
b) Perform appropriate calibration procedure
(page 17)
c) Replace amplifier
3. Space Temperature Selector
(CE-Smart
TM
)
a) Induced voltage in field wiring
a) Utilize shielded, twisted pair wiring