1 9 |
P a g e
Missing or incorrect
lamp key.
Ensure the lamp key
(packed with the lamp, on
the connector) is installed.
Unplug and reinstall the
key. Ensure the key part
number matches Lamp on
Maintenance Parts screen.
Soft Alarms:
The following remaining errors give a 15 second audible chirp only
System Display
Problem
Resolution
The module indicated is
no longer communicat
-
ing to with the system.
Ensure all modules are
connected properly to the
system and to each other.
Modules can be tested
individually by plugging in
one at a time and cycling
power to the system.
Replace any module that is
not detected when plugged
directly into the controller.
Warning:
After any hard alarm, the home or facility should be disinfected. Follow the steps
under the “System Disinfection” heading.
Boil Water Advisory
: If any failure occurs on a CalUltra UV system, the water
must not be used for human consumption until the system is returned to a
safe operational mode. If the water is used for human consumption during this
period, the water must be boiled (minimum 20 minutes at a full boil)
prior to
consumption.