background image

MI182 REV.8   Page 1 of 2

CCI Thermal Technologies Inc.  2721 Plymouth Drive, Oakville, ON L6H 5R5  Tel. (905) 829-4422  Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3  –  INFRARED RADIANT HEATERS

FIRE/EXPLOSION  HAZARD  WARNING  -  During  operation,  take  precautions  to  ensure  that

combustible materials are always kept at a safe distance from the radiant energy.  This heater is

not  intended  for  use  in  hazardous  areas  where  flammable  vapours,  gases  or  liquids  or  other

combustibles are present.  Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures.  If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations.  Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion.  The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage.  Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum  space  clearances  from  combustibles,  when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the  safety  of  this  equipment  and

adequate back-up controls and safety

devices must be installed.  Failure to

comply could result in personal injury

and/or property damage.

Heaters  must  be  wired  by  qualified

personnel  in  compliance  with  local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply.  Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation  contamination  or  moisture

accumulation  can  cause  fault  to  the

element sheath generating arcing and

releasing molten metal.  Install proper

ground  fault  protection  to  prevent

personal  injury  and/or  property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply  conductors  to  the  heater  must  be  suitable  for

110°C(230°C).  The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1".  The standard Type 1 enclosure

is  suitable  for  dry,  indoor  locations  only  in  non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes  located  at  each  top  corner  of  the  housing.  Either  chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support  (slotted  holes)  is  adequate  provided  that  the  spacing

instructions as given in 3.0 are followed.  Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

 cm

[12”

]

FIG. 1  –  MOUNTING CLEARANCES

MI182 REV.8   Page 1 of 2

CCI Thermal Technologies Inc.  2721 Plymouth Drive, Oakville, ON L6H 5R5  Tel. (905) 829-4422  Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3  –  INFRARED RADIANT HEATERS

FIRE/EXPLOSION  HAZARD  WARNING  -  During  operation,  take  precautions  to  ensure  that

combustible materials are always kept at a safe distance from the radiant energy.  This heater is

not  intended  for  use  in  hazardous  areas  where  flammable  vapours,  gases  or  liquids  or  other

combustibles are present.  Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures.  If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations.  Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion.  The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage.  Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum  space  clearances  from  combustibles,  when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the  safety  of  this  equipment  and

adequate back-up controls and safety

devices must be installed.  Failure to

comply could result in personal injury

and/or property damage.

Heaters  must  be  wired  by  qualified

personnel  in  compliance  with  local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply.  Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation  contamination  or  moisture

accumulation  can  cause  fault  to  the

element sheath generating arcing and

releasing molten metal.  Install proper

ground  fault  protection  to  prevent

personal  injury  and/or  property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply  conductors  to  the  heater  must  be  suitable  for

110°C(230°C).  The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1".  The standard Type 1 enclosure

is  suitable  for  dry,  indoor  locations  only  in  non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes  located  at  each  top  corner  of  the  housing.  Either  chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support  (slotted  holes)  is  adequate  provided  that  the  spacing

instructions as given in 3.0 are followed.  Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

 cm

[12”

]

FIG. 1  –  MOUNTING CLEARANCES

MI102 REV.7.01  Page 3 of 8

8.0 NORMAL SEQUENCE OF OPERATION
8.1 

The heater must be properly mounted and wired in accordance 

with these instructions, terminal cabinet door closed and secure, 

fan blade free, and no obstructions to air inlet or outlet areas.

8.2 

Energize the heater at the rated supply voltage.

8.3

 Assuming the thermostat is calling for heat OR the thermostat 

is turned to a higher temperature than ambient:

8.3.1

 The main contactor(s) will energize the elements.

8.3.2

 The fan motor will not start immediately.

8.3.3

 After a delay of 20-50 seconds, the fan contactor will operate

and the fan will start. See paragraph 3.6 for proper fan rotation.

8.4 

After the ambient temperature rises to the operating point of 

the thermostat, the thermostat contact will open.

8.4.1 

The main contactor(s) will de-energize the elements.

8.4.2

 The fan motor will continue to operate, purging the residual 

heat from the elements.

8.4.3

 After a delay of 20-70 seconds, the fan contactor will open 

and the fan will stop.

8.5

 The cycle described in 8.3 will repeat.

9.0 MAINTENANCE

The GX unit heater is constructed to operate in tough industrial 

applications with a minimum of maintenance. 

However, some routine maintenance is recommended to extend 

the life of the heater and its components. Always disconnect the 

electrical source before performing any maintenance.

9.1

 TERMINAL ENCLOSURE - At periodic intervals, of not 

more than one year, open the terminal enclosure to inspect for 

cleanliness and dampness. Vacuum any dust and wipe up any 

moisture. Check all electrical connections and tighten if necessary.

9.2 

CONTACTOR(S) - Inspect the contacts carefully and replace 

the contactor(s) if excessive wear is becoming evident. Contacts 

which are not pitted can be cleaned using a fine grade sandpaper 

or emery cloth.

9.3

 MOTOR - The motor supplied is rated at 1/3 HP with totally 

enclosed construction and sealed ball bearings. These motors are

“permanently” 

lubricated by the manufacturer. Internal thermal 

protection is provided to eliminate motor overheating. Check all 

motor mounts and tighten if necessary.

9.4 

FAN BLADE - Visually inspect the fan blade to ensure accidental 

damage has not occurred. If bent or damaged, a factory balanced 

blade should be installed so that the rated air flow is maintained. A 

damaged fan blade may not deliver the required air flow over the 

elements, resulting in short cycling of the internal contactors by the 

high limit control. This condition will significantly shorten the life of 

the contactors. Check to ensure the fan blade is tightly fastened to 

the motor shaft.

9.5

 HEATER PAINT FINISH - The GX unit heater is finished with 

an epoxy paint to provide maximum resistance to corrosion due 

to airborne contaminants. We recommend the cabinet be wiped 

down periodically using a mild detergent.

8.0 SÉQUENCE NORMALE D’OPÉRATION
8.1

  L’appareil  doit  être  installé  et  raccordé  selon  les  normes 

recommandées pour ce type d’appareil, i.e. Porte du boîtier de 

contrôle fermée et verrouillée, aucune obstruction à l’entrée et à la

sortie de l’air, et l’éventail non obstrué.

8.2

 Mettez l’appareil sous tension (voir la plaque signalétique pour 

tension d’opération).

8.3

 En assumant que le thermostat ets en position de demande 

ou  que  le  point  de  consigne  est  plus  élevé  que  la  température 

ambiante:

8.3.1 

Le(s) contacteur(s) principal actionne l’opération des 

éléments chauffants.

8.3.2

 Le ventilateur ne partira pas immédiatement.

8.3.3 

Après un délai de 20-50 secondes, le ventilateur se mettra 

en  marche.  Voir  paragraphe  3.6  pour  la  rotation  adéquate  du 

ventilateur.

8.4 

Dès que la température ambiante atteindra le point de consigne 

du thermostat, les contacts de celui-ci s’ouvrent.

8.4.1

 Le contacteur principal coupe l’opération des éléments 

chauffants.

8.4.2

 Le ventilateur continue de tourner jusqu’à ce que la chaleur 

résiduelle de l’appareil est évacuée.

8.4.3 

Après un délai de 20-70 secondes, le ventilateur s’arrêtera.

8.5 

Le cycle décrit au paragraphe 8.3 reprendra.

9.0 ENTRETIEN

L’appareil  GX  est  conçu  et  fabriqué  pour  les  applications 

industrielles robustes exigeant une maintenance minime. 

Cependant, une maintenance routinière est recommandée 

afin  d’accroître  la  durabilité  de  l’appareil  et  de  ses  composants. 

Débranchez toujours l’appareil avant de procéder à l’entretien.

9.1

 BOÎTIER DE CONTRÔLE - À intervalles réguliers, au moins 

une fois par année, ouvrez le boîtler de contrôle pour vous assurer

de la propreté et de l’étanchiété. Débarrassez de toutes poussières

et  asséchez  si  nécessaire.  Vérifiez  également  la  fermeté  des 

connexions électriques.

9.2 

CONTACTEUR(S)  -  Vérifiez  les  contacts  soigneusement  et 

remplacez s’il y á usure excessive. Sinon, nettoyez les contacts en 

utllisant un papier sablé fin ou linge d’émeri.

9.3

 MOTEUR - Moteur de 1/3 C.V., Totalement fermé avec 

roulement à billes, lubrication permanente par le manufacturier et 

protection thermique intégrale. Vérifiez les points de montage et 

reserrez si nécessaire.

9.4

 ÉVENTAIL - Procédez à une inspection visuelle et assurez 

vous que les palles ne sont pas endommagées. Si elles sont pliées 

ou endommagées, remplacez par un nouvel éventail balancé 

en  usine  afin  d’obtenir  le  débit  d’air  spécifique  de  l’appareil.  Un 

éventail endommagé peut entrainer une surchauffe de l’appareil 

et un cyclage répétitif de la protection haute-limite. Ce cyclage 

provoquera  l’usure  prématurée  des  contacteurs.  Assurez-vous 

que l’éventail est ancré solidement à l’arbre du moteur.

9.5 

FINI EXTÉRIEUR DE L’APPAREIL - L’appareil GX est

recouvert d’un fini 

“epoxy”

 pour vous assurer une plus grande

résistance à la corrosion due aux contaminants de l’air. Essuyez

le cabinet de l’appareil avec un détergent doux annuellement.

Summary of Contents for GX152

Page 1: ...trol cabinet door Also refer to Fig 5 for typical wiring INSTALLATION AND OPERATING INSTRUCTIONS INSTRUCTIONS D INSTALLATION ET D OP RATION TYPE GX UNIT HEATERS A ROTHERMES ULTRA ROBUSTES MOD LE GX 1...

Page 2: ...led with proper fast acting fuses or breakers as close as possible to the ratings indicated on the nameplates in compliance with the local electrical codes 4 0 To facilitate mounting the heater has fo...

Page 3: ...pe 1 enclosure is suitable for dry indoor locations only in non corrosive environments 9 0 For short circuit protection heaters must be installed with proper fast acting fuses or breakers as close as...

Page 4: ...E NO PHASE L MENT MOTEUR TRANSFORMATEUR 50 VA C CONTACTEUR Bobine 240V VENTAIL Secondaire 240V 3 Required Requis 1 Required Requis GX152 208 3 KXF10008 25 B11085 01 NONE AUCUN C11055 02 GX153 240 1 KX...

Page 5: ...PERATION AND MAINTENANCE INSTRUCTIONS FOR SERIES OK3 INFRARED RADIANT HEATERS FIRE EXPLOSION HAZARD WARNING During operation take precautions to ensure that combustible materials are always kept at a...

Page 6: ...L6H 5R5 Tel 905 829 4422 Fax 905 829 4430 www ccithermal com ISO 9001 2000 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR SERIES OK3 INFRARED RADIANT HEATERS FIRE EXPLOSION HAZARD WARNING Dur...

Page 7: ...m the date of installation The Company neither assumes nor authorizes any person to assume for it any other obligation or liability in connection with the product s The Purchaser agrees that all warra...

Page 8: ...application inappropri e ou un d faut d alignement des pi ces Aucune garantie ne s applique la finition de peinture except dans le cas de d fauts de fabrication apparen ts dans les 30 jours compter de...

Reviews: