LOOP CONFIGURATION TOOL (LCT)

The Loop Configuration Tool model LCT is a configuration adapter
for ExTemp infrared temperature sensors.

It is designed to be connected to the 4 to 20 mA current loop on
the safe side of an Intrinsically Safe isolator, and to a Windows PC
via USB.

This manual describes how to connect the LCT and use it to
configure the sensor. For information on connecting and using
the sensor itself, please refer to the previous sections of this
manual.

WARNING

This device MUST NOT be used in hazardous areas. It is not certified for use in
explosive atmospheres and may only be connected on the safe side of a
suitable, certified Intrinsically Safe isolator.

Do not attempt to repair a faulty unit. Contact the vendor to arrange a return.

ELECTRICAL CONNECTION

Connect the device to the 4 to 20 mA measurement loop via the hook-type connectors. For
reliable communications, the total resistance R

L

on the 4 to 20 mA loop should be within the

range specified on the connection diagrams. You may need to connect a resistor in series with
the existing measurement instrumentation on the 4 to 20 mA loop to ensure this.

WIRE IDENTIFICATION - LCT

The LCT connectors are colour coded as follows:

Colour of Wire and Hook Connector

Polarity

Red

+

Black

-

Measurement
instrumentation

LCT

PC with
software

Power supply

Hazardous Area
(All Zones IIC and IIIC)

Safe Area (Non-
Hazardous)

Intrinsically Safe
isolator

To the sensor

14

Summary of Contents for ExTempMini Series

Page 1: ...ExTempMini Series Intrinsically Safe Miniature Infrared Temperature Sensor with Separate Electronics Module Operator s Guide...

Page 2: ...ty i IMPORTANT INFORMATION FOR USE Voltage MUST be supplied by a suitably rated safety isolator For re configuration of the sensor the LCT MUST be connected in the safe area behind the protection of a...

Page 3: ...rsist for a short period NO Group Definition Supported Gas IIA e g Propane IIB e g Ethylene IIC e g Hydrogen Dust IIIA Combustible flyings NO IIIB Non conductive dusts NO IIIC Conductive dusts NO Tabl...

Page 4: ...ge may be rescaled between limits 20 C and 1000 C via optional adapters and software Sensing Head Cable Length m e g 5 5 m 10 10 m 25 25 m maximum length The sensing head and electronics module are ca...

Page 5: ...ntal Rating IP65 NEMA 4 IP65 NEMA 4 Ambient Operating Temperature Range 0 C to 70 C 0 C to 180 C Ambient Pressure Range 80 kPa 0 8 bar to 110 kPa 1 1 bar 80 kPa 0 8 bar to 110 kPa 1 1 bar Relative Hum...

Page 6: ...8 V Maximum Input Current Ii 93 mA Maximum Input Power Pi 0 651 W Maximum Internal Capacitance Ci 5 17 nF Maximum Internal Inductance Li 1 99 H ATEX Certificate Number CML 22ATEX2007X IECEx Certificat...

Page 7: ...ended sensing head cable 25 m max factory fitted contact Calex for information about extending the cable Output cable 25 m max factory fitted cable alternatively customer may supply and fit output cab...

Page 8: ...ontaminate the lens and cause errors in temperature measurement In these types of environment the air purge collar should be used to help keep the lens clean Electrical Interference To minimise electr...

Page 9: ...way from the lens It must be screwed on fully There are two models of air purge collar to suit the different optics see below Air flows into the hose barb fitting and out of the front aperture Air flo...

Page 10: ...adapter PC with configuration software Load measurement instrumentation 220 Vs Do not open PWR PWR Sensing head Ta 20 C to 180 C Certified Intrinsically Safe isolator e g connections shown are for MT...

Page 11: ...MODBUS The optional LCT 485 Network Interface not shown allows an ExTemp sensor to be connected to an RS 485 Modbus RTU network for temperature measurement configuration and data acquisition Each LCT...

Page 12: ...ing can be applied by setting Hold Mode to Peak or Valley and setting the hold period This is useful if the temperature reading is interrupted by gaps between moving objects or by an obstruction Defau...

Page 13: ...for further advice LENS CLEANING Keep the lens clean and dry at all times Any foreign matter on the lens would affect measurement accuracy Blow off loose particles if not using the air purge accessory...

Page 14: ...safe side of a suitable certified Intrinsically Safe isolator Do not attempt to repair a faulty unit Contact the vendor to arrange a return ELECTRICAL CONNECTION Connect the device to the 4 to 20 mA...

Page 15: ...ARE See Configurable Parameters and the Configuration Software diagram opposite If the Settings icon is greyed out the software is locked Unlock the software to allow access to the Settings menu The d...

Page 16: ...twork interface Select COM port then select LCT 485 on the next screen Emissivity Compensation Temperature List Temperature Display Output Range Output Processing Default Password 1234 Connection List...

Reviews: