Troubleshooting

Under normal operating conditions the Caleffi TankMixer™ 520 series thermostatic mixing 
valve will provide a very high level of performance. However, in some circumstances, where the 
following maintenance schedule is not followed problems may arise.

Recommended maintenance schedule:

Tests should be conducted regularly to monitor the thermostatic mixing valve performance, 
as deterioration of performance could indicate that the valve and/or the system require 
maintenance. If, during these tests, the temperature of the mixed water has changed 
significantly in comparison with the previous test, the details given in the installation and 
commissioning sections should be checked and maintenance conducted.
The following should be checked regularly to ensure that the optimum performance levels of 
the valve are maintained. Check every 12 months at least, or more often if necessary.
1) Check and clean the system filters.
2) Check that any check valves positioned upstream of the Caleffi thermostatic mixing valve are 
operating correctly, without problems caused by impuritites.
3) Limescale can be removed from internal components of the thermostatic mixing valve by 
immersion in a suitable de-scaling fluid.
4) When the components which can be maintained have been checked, commission the valve.

Symptoms

Cause

Corrective action

Hot water at the cold taps

a) Operation of check valve is 

hindered; Check valve is not 

sealing correctly. 

b) Check valves not fitted.

- Replace faulty check valve

Fluctuating mixed water 

temperature

a) Erratic supply temperatures at 

the inlet of the valve. 

b) Starvation of the water 

supplies at the inlets of the valve. 

c) Incorrect commissioning of the 

valve.

- Restore inlet conditions within 

the limits of the valve.

Erratic flow of water from 

the valve

a) Insufficient water supplies 

b) Fluctuations in the supply 

pressures/temperatures. 

c) Adverse effect created by other 

draw off points on the system

- Stabilize inlet supply condi-

tions.

No flow of water from the 

valve

a) In-line filers blocked. 

b) Insufficient supply pressures. 

c) Debris obstructing valve 

operation.

- Clean filters 

- Resore inlet supplies 

- Clean debris or scale from 

the valve.

Valve shut-off function not 

performed when tested

a) Installation not compliant with 

instructions. 

b) Minimum temperature differ-

ence not reached. 

c) Valve mechanism blocked 

by dirt.

- Follow installation instructions. 

- Increase hot water 

temperature. 

- Remove dirt/limescale from 

the valve.

Summary of Contents for TankMixer 520 Series

Page 1: ...lve angle body with cold water tee and flexible connector connections NPT female to water heater sweat press and NPT male union mix outlet cold water inlet 52051_AX series kit 52050_AX series kit with mixed outlet temperature gauge 520051A Adjustable three way thermostatic mixing valve angle style body only for field installed connection fittings source separately connections 1 male union Technica...

Page 2: ...missioning and maintenance of the TankMixer thermostatic mixing valve take the necessary precautions to ensure that such temperatures do not endanger people CAUTION In the case of highly aggresive water arrangements must be made to treat the water before it enters the thermostatic mixing valve in accordance with current legislation Otherwise the thermostatic mixing valve may be damaged and will no...

Page 3: ...er temperature and safely delivered at lower adjustable temperatures to all fixtures In addition it can be used to reduce legionella growth by allowing the water heater thermostat to be set at 140 F The flexible hose length allows mounting to all water heater tank sizes The TankMixer 520_AX series comes standard with a recirculation port that can be plugged or used for connecting to a hot water re...

Page 4: ... failure the shutter seals off the hot water passage thus preventing the delivery of mixed temperature water This is only guaranteed when there is a minimum temperature difference between the inlet hot water and the mixed temperature water delivery of 27 F Water heater As a result of the NAECA many water heaters now have more insulation making them physically larger for the same water capacity tha...

Page 5: ... installed in any position either vertical or horizontal or upside down The following are shown on the thermostatic mixing valve body Hot water inlet color red and marked HOT Cold water inlet color blue and marked COLD Mixed water outlet marked MIX Locking the setting Position the handle to the number required with respect to the index point Unscrew the head screw pull off the handle and repositio...

Page 6: ...that the temperature is set using a suitable calibrated digital thermometer The valve must be commissioned by measuring the temperature of the mixed water emerging at the point of use 3 The maximum outlet temperature from the valve must be set accounting for fluctuations due to simultaneous use It is essential for these conditions to be stabilized before commissioning 4 Adjust the temperature usin...

Page 7: ...UPPLY SYSTEM WITHOUT RECIRCULATION HOT WATER STORAGE T Ball valve Ball valve with check valve Temperature gauge Pump Expansion vessel Thermostat Temperature pressure safety relief valve Safety relief valve Pressure reducing valve Y strainer T MAIN WATER SUPPLY MAIN WATER SUPPLY MAIN WATER SUPPLY ...

Page 8: ...used by impuritites 3 Limescale can be removed from internal components of the thermostatic mixing valve by immersion in a suitable de scaling fluid 4 When the components which can be maintained have been checked commission the valve Symptoms Cause Corrective action Hot water at the cold taps a Operation of check valve is hindered Check valve is not sealing correctly b Check valves not fitted Repl...