Parameter
Description
Setting Range
Factory (default)
configuration
SETSH
Setpoint for Ta (mixed outlet water temperature) during
shock phase.
86 - 185°F
30 - 85°C
140°F
tSH
Duration of thermal shock phase to be started manu-
ally by the user
1 to 4320 min
005 min
Countdown
Countdown before activating thermal shock
0 to 999 min
0001 min
Activate countdown
Enables activation of countdown before thermal shock
NO= not active
YES= active
NONE
Parameter
Description
Setting Range
Factory (default)
configuration
tPLAY
Delay due to gap in mechanical components during
actuator movement, until the internal valve ball starts
to move in the opposite direction.
from 0 to 255 sec
in 1 sec steps
005 sec
tMOTOR
Time required for the actuator to move the valve from
the full closed to the fully open position. Default setting
is recommended for all applications, do not change.
Consult Caleffi otherwise. (This is NOT motor stroke
time)
from 8 to 320 sec
in 2 sec steps
100 sec
ANTI-CLOG
Ball rotation cycle to clean deposit formation for
efficient operation. To deactivate enter release code
5566 and confirm with ON-OFF.
ON
OFF
ON
Cels.-Fahr.
Temperature units.
°F
°C
°F
Thermal shock
Temperature History
Temperat. History, read only. See Log section, next.
21