Technical data
Temperature range
Operative: +5°C - +35°C
Storage: +5°C - +45°C
Protection degree: IP 40 (EN60529)
Protection class: II
Fastening: wall clipped
Dimensions: LxHxP 160x160x35 mm
Power supply: 100..240Vac 50/60Hz
USB (5Vdc, 500mA) for commissioning
Consumption: 4.5 W
Radio frequency: 868 MHz – Max transmission power: 27dBm
Wireless M-Bus mode: C1+T1+T2+, S1+T1, T1+T2+, T1
Max distance between two repeaters: 500mt free field – 40mt in
building
Troubleshooting
1)
The device does not start:
-
in case of network power supply, check that the power
is on;
-
in case you are using a USB port, check the USB cable
quality and that the PC is enabled to handle 500 mA of
electrical power.
2)
The blue led light does not stop flashing:
-
check that the device Data Easy
+
is on and that the
repeater is connected and in good position (avoid
placing it in switchboards or shielded environments);
-
check that repeater is at least 5 meters distant from
Data Easy
+
and from other repeater;
-
check that the ID and the MESH network channel are
correct using Data Easy Toolkit software and are the
same ones used by Data Easy
+
.
3)
Not all the devices are found:
-
check that the devices that were not found are not too
distant from repeaters or that the signal is not shielded
by thick concrete or metal walls;
-
check that the OMS/Wireless M-Bus transmission is
active in the devices. Caleffi devices (MONITOR 2.0 -
2.0 E - PULSE) can be activated with the
parameterization or read function using the SW7200
software and the WSL868 USB / Radio key. Consult
the appropriate manual;
-
check that the MESH network is working using the Data
Easy
+
web interface.
Safety
The Data Easy
+
data logger and the repeater must be installed by a qualified installer in accordance with national
regulations and / or local requirements.
Warnings for the correct disposal of the product
The symbol shown on the side is affixed to the data logger cod. 720081 and on the repeaters cod. 720082 to indicate that these
products can not be treated as municipal waste. The data logger and the repeaters, in fact, are among the equipment for which
the European Directive on waste electrical and electronic equipment (WEEE) is applied. There is therefore an obligation not to
dispose of appliances as municipal waste and to carry out separate collection. It is also necessary to comply with national legal
provisions regarding equipment collection systems.
Declaration of conformity
The manufacturer, Caleffi S.p.A., declares that the types of radio equipment cod. 720081, 720082 comply with Directive 2014/53 / EU (RED) and
2011/65 / EU (RoHS)
Declarer:
CALEFFI S.P.A.
S.R. 229, n. 25 28010 Fontaneto d'Agogna (NO) - Italy Tel. +39 0322 8491 / Fax +39 0322 863305
Models: 720091 - 720092 - 720093
Marking: CE
We reserve the right to make improvements and changes to the described products and related technical data at any time without notice.
CALEFFI S.p.A.
S.R.229, N.25 28010 Fontaneto d’Agogna (NO) · Italy
Tel. +39 0322 8491 · Fax +39 0322 863723
www.caleffi.com · [email protected]
© Copyright 2018 Caleffi