Special cases of use 

The  following  image  shows  an  installation  in  which  either  due  to 
network layout reasons or for a number of devices exceeding 500 (Max 
500  for  each  Data  Easy  +),  it  is  necessary  to  create  four  different 
networks of repeaters. 
The  following  applies  also  when  the  number  of  networks  is  2,  3  or 
higher than 4.  

Important!

 It is recommended not to change the MESH network channel 

(default =13 both on Data Easy 

and on repeaters), because the change 

may involve the transmission power of the devices. 

Network configuration 

1.

Power on Data Easy

+

, connect to web interface and start the

search  of  devices  following  the  "User  guide  Data  Easy

+

"

manual.

2.

Activate the OMS/Wireless M-Bus trasmission in the devices
trough  the  parametrization  or  reading  following  the  "User
guide Data Easy

" manual.

3.

Power on the first repeater to be installed and move it away
to a minimum distance of 5 meters from Data Easy

+

.

4.

Fixed blue repeater LED shows the connection to the MESH
network.

5.

Once connected, it shows the MESH radio signal quality to
the  gateway,  by  turning  on  the  green  front  LED,  1  -
insufficient reception, 2 - sufficient, 3- good, 4 - excellent.

6.

Place repeater in a place where the reception signal is >=2
and  the  reception  of  all  the  Wireless  M-Bus  devices  you
expect to receive with this repeater is satisfactory.

7.

Check through Data Easy

 web that Wirelss M-Bus devices,

that you want to receive, reach the repeater.

8.

Fasten  the  repeater  and  proceed  with  powering  a  second
repeater  keeping  it  at  least  5  metres  away  from  both  the
repeater and Data Easy

.

9.

Once connected, it shows the MESH radio signal quality to
the gateway, by turning on the front LED, so proceed as for
the first repeater.

The default scanning phase is 13 hours. Is possible to modify 
its duration through Data Easy

+

 web server. 

Is possible to have various independent repeaters networks in 
the same building, in that case, you need to have different ID 
or  channel  for  each  repeater  group  and  the  relative  Data 
Easy

+

. You can modify these parameters through Data Easy 

Toolkit software installed on a PC and connect via mini USB 
cable to repeater, see the "User guide Data Easy

" manual for 

details. 

Settings of MESH network ID 

In  order  to  avoid  interferences  between  the  various  systems, 
assign  to  each  Data  Easy

+

  a  different  MESH  network  ID.  The 

setting is done on Data Easy

+ ”

 through its web interface with the 

following  way: 

“Settings  /  Wireless  Devices  /  Device  search  /  Setup  Mesh 
Network”. 

The same MESH network ID setting must be carried out also on all 
repeaters that are part of the network of the Data Easy

which they 

have to communicate with. 
For this procedure it is necessary to connect a PC to the repeater 
to be configured (via mini USB cable), use the Data Easy Toolkit 
(installation programs available on the Caleffi USB stick supplied)  
and follow the instructions in the "User guide Data Easy

" manual. 

Note

: lt  is 

recommended 

not  to  change  the  MESH  Netwo

r

Channel  (defau

lt 

1

3 bot

on 

Data Easy

+

 

and on repeaters), 

because 

the 

change 

may involve 

the transmission power of 

th

devices. 

Repeaters firmware upgrade 

You should always check for an updated release of the firmware of 
the repeaters. The one installed during the production phase might 
be obsolete. 
Far this procedure it is necessary to connect a PC to the repeater 
to  be  configured  (via  cable  USB).  Use  the  Data  Easy  Toolkit 
software (installation programs available on the Caleffi USB stick 
supplied) and follow the instructions in the manual.