background image

Commissioning 

After  installation,  the  mixing  valve  must  be  tested  and  commissioned  by  an  authorised  technician  in
accordance with the procedure given below and as specified by current applicable legislation.
The following instructions must be read and understood before commissioning the mixing valve of Caleffi 262
and 263 series kits.
If  there  are  any  aspects  of  the  installation  or  the  system  which  do  not  correspond  to  the  specified
requirements, the valve must not be commissioned until the installation/system is made to conform to the
said requirements.

1) Make sure that the system is clean and free from dirt before commissioning the thermostatic mixing valve.

2) It is recommended to set the mixed water temperature with a calibrated digital thermometer. The valve

must be commissioned by measuring the mixed water temperature at the user tap outlet.

3) Depending  on  the  intended  use  and  associated  risk,  the  oulet  temperature  must  be  adjusted  so  as  to

avoid any danger for the user and comply with applicable legislation.

4) The temperature at the valve outlet must be adjusted by taking into account any potential fluctuations caused by simultaneous water drawing off.

These conditions must be stabilised before the valve is commissioned.

5) The temperature may be adjusted using the control knob on the mixing valve.
     a) Adjust the temperature of the mixed water to the desired value.
     b) Measure and record the temperature at the cold and hot water inlets.
     c) Measure and record the temperature of the water at the tap outlet at the lowest and highest flow rate.
     d) Perform a test of the anti-scald thermal shut-off function.

         Close the shut-off valve at the cold water inlet and check the mixed water outlet. The flow rate at the outlet should quickly drop to zero.

     e) Measure and record the maximum mixed water temperature. The temperature may not exceed the values permitted in any applicable legislation

or code of practice.

     f) Restore the cold water inlet supply and measure the water temperature at the outlet after it has stabilized. The final temperature measured in

this test may not exceed the permitted values ±2°C.

It is recommended to register all the above information in the commissioning report and updated in the maintenance report whenever the valve is
worked on.

Assembly

1.

  Remove the protective cover.

2.

 Connect the system connection pipes to the kit with mixing valve;

3.

 Fit the protection cover onto the kit with mixing valve;

4.

 Connect the pipes to the boiler.

Factory configurations 

Diverter valve:                           45°C
Thermostatic control device:     30°C

Temperature setpoint adjustment

The  diverter  valve  is  factory  set  to  operate  at  a  temperature  of  45°C,  diverting  water  to  the  boiler  if  the
temperature is lower than this setpoint value. The set temperature value is fixed using a locking ring.

The  263  series  thermostatic  control  device  is  factory  set  and  fixed  to  keep  constantly  at  30°C  the
temperature of the water at the boiler inlet.

2

3

4

Reviews: