background image

* Masonry Mass refers to any dry pack, self leveling
product, light weight bedding mortar, and all mortar
based aggregates.

** To secure the cable use either hot melt glue,
cable clips, or 3/8’’ crown staples. Or put down wire
mesh and secure with wire ties or duct tape.

*** Finished flooring refers to tile, marble, or radiant
compliant carpet, hardwood, and laminates.

This SPACING FORMULA must be used to calculate spacing between cables.

AREA (sq. ft.) x 12 ÷ LENGTH OF CABLE = On Center SPACING

(Cable length noted on UL tag.)

Example:

Area In Square Feet

=

85 sq.Ft.

85x12= 1020 = 5.28” On Center

Cable Length

=

193 Ft.

193

Quality & Comfort from the Ground Up

1507 B WEST PARK AVE. PERKASIE, PA 18944

PHONE: 215-453-9228

FAX: 215-257-7399

ORBIT MANUFACTURING COMPANY

TXLP/2R Series Electric Floor Heating Cable Instructions

Installation Of The Heating Cable

I

MPORTANT NOTE: THESE CABLES ARE NOT TO BE INSTALLED IN WALLS OR CEILINGS FOR ANY REASON

AND ALL ELECTRICAL CONNECTIONS MUST BE PERFORMED BY A QUALIFIED, LICENSED ELECTRICIAN.

GROUND RATED INSULATION

***FINISHED FLOORING

REINFORCED CONCRETE

**HEATING CABLE, IN NEW SLAB
OR ON TOP OF EXISTING SLAB.
MAXIMUM 2’’ FROM SURFACE.

SLAB CONSTRUCTION

CRUSHED ROCK OR STONE

Typical Cable Installations

HARDWOOD FLOORING

SUB-FLOOR
(SLAB OR PLYWOOD)

HEATING CABLE

NAILS

*MIN. 5/8" MASONRY MASS

(ASSURE NO AIR GAPS)

SLEEPERS

HARDWOOD FLOORS, ONE
COVERING, MINIMAL THICKNESS

INSULATION

INSULATION
(OPTIONAL, RECOMMENDED)

***FINISHED FLOORING

SUB-FLOOR PLANKING

**HEATING CABLE
(*

) MASONRY MASS

MIN. 5/8”

FRAME CONSTRUCTION

(OPTIONAL)

(OPTIONAL)

Cold lead “

”, marked about 7’ from the start of cable.

Splice

Actual “

” located between the splice and bulb.

Heating Cable

The TXLP/2R Series Cable box sets are pre-engineered units available
for both 120 and 230 volt applications. Each cable has a specific length,
wattage, and ohms resistance reading. It is important that you supply
the TXLP/2R Heating Cable with the voltage it is designed and tagged
for. The heating cables are factory designed under precise specifications
and cannot be altered for any reason and are not interchangeable with
other cable.

as this will damage the cable and void the warranty. Both splices

be buried in the masonry. These are the points where the cable is

attached to the cold lead, and on the opposite end where the heating
cable ends with the bulb. Note the thickness of the bulb when pouring
your flooring material to embed the cable. Only the cold leads can be out
of the masonry or concrete and run into the conduit.

IT IS VERY IMPORTANT TO NEVER CUT THE HEATING

CABLE
MUST

‘‘

’’ located on the end of

the heating cable.

Bulb

‘’

’’ identified by asterisks,

located at the beginning of the cable.

Cold Lead

******DO NOT CUT THE HEATING CABLE******

*Identifying the Nexans TXLP Manufactured Heating Cable*

ALWAYS:

Follow local and national electrical codes.
Test the cable for the proper readings before, during and
after the installation.
Make certain both splice and bulb are buried in the pour.
Fill out the warranty card and return it to Orbit.

NEVER:

Cross the blue heating cable over itself.
Cut the blue heating cable for any reason.
Run blue heating cable directly into the junction box.
Subject any part of the cable to harmful surfaces.

Reviews: