4.1.14 Tube collector special function

If the controller measures an increase of 4 °Ra compared 
to the collector temperature tankd at last, the solar 
pump is switched-on to 100 % for about 30 seconds. 
After expiration of the solar pump runtime the current 
collector temperature is tankd as new reference value. If 
the measured temperature (new reference value) is again 
exceeded by 4 °Ra, the solar pump again switches-on for 30 
seconds. If the switch-on difference between collector and 
tank is again exceeded during runtime of the solar pump 
or the standstil of the system, the controller automatically 
switches over to solar charging.
If the collector temperature drops by 4 °Ra during standstill, 
the switch-on value for the special tube collector function 
will be recalculated.

O TC: 
Tube collector special 
function  
Adjustment range: 
OFF ... ON 

 

Factory setting: OFF

The thermostat function works independently from the solar 
operation and can e.g. be used for use of surplus energy or 
an after-heating. 

• 

AH O AH F 
the thermostat function is used for after-heating

• 

AH O > AH F 
the thermostat function is used for use of surplus 
energy

On the display is shown 

 if the second relay output is 

activated.

4.1.15 Thermostat function 

(Arr = 2)

after-heating

use of surpluse energy

AH O:
Thermostat-switch-on 

 

 tem perature
Adjustment range: 
32 ... 203 °F
Factory setting: 104 °F

AH F:
Thermostat-switch-off  tem-
pe rature
Adjustment range: 
32 ... 203 °F
Factory setting: 113 °F

For control and service work the operating mode of the 
controller can be manually adjusted by selecting the adjust-
ment value HAND, in which the following adjustments can 
be made:

4.1.16 Operating mode

•  HAND

 

Operating mode 
OFF 

relay off 

 (flashing) + 

  

AUTO  : 

relay in automatic operation 

ON 

relay on 

 (flashing) + 

 

HAND1,HAND2:
Operating mode 
Adjustment range:  
OFF, AUTO, ON
Factory setting: AUTO

4.1.17  Language

The menu language can be adjusted in this channel.

• 

dE  :  German

  En  :  English

•  It  :  Italiano
•  Fr  :  French

LANG:
Adjustment of language
Adjustment range: dE, En, It
Factory setting: En

4.1.18  Unit

The menu unit can be adjusted:

•  °FAH
  °CEL

UNIT:
Adjustment of unit
Adjustment range: FAH, °C
Factory setting: FAH

Summary of Contents for iSolar 3

Page 1: ...Thanks for buying this product Read this manual carefully to get the best perfomance from this unit Mounting Connection Handling Fault localization Examples manual 49005100 49005100...

Page 2: ...micro films and the storage into electronic systems Editor CALEFFI NORTH AMERICA Inc Important notice We took a lot of care over the texts and drawings of this manual and to the best of our knowledge...

Page 3: ...4 F Size 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Display System screen for sys tems visualisation 16 segment display 7 segment display 8 symbols for system stat...

Page 4: ...lief supports and screws Depending on the version the controller is equipped with 2 relays to which the consumers e g pumps valves etc can be connected Relay 1 18 conductor R1 17 neutral conductor N 1...

Page 5: ...nsors and after heating The sensor S4 TRF can optionally be used for heat quantity balancing Arr 2 1 2 2 Allocation of clamps for system 2 Symbol Specification S1 collector sensor S2 tank sensor below...

Page 6: ...d for scrolling forward through the indication menu or to increase the adjustment values The backwards key 2 is accordingly used for the reverse function For adjustment of last indication channel keep...

Page 7: ...he flow direction or the current bre aking capacity are always shown Heating circuit Tank 1 and 2 with heat exchanger After heating with burner symbol Temperature sensor 2 2 3 System screen only syste...

Page 8: ...types of antifreeze Corresponding channel is only available if the option heat quantity measurement is deactivated OWMZ Please note S3 and S4 are only indicated if sensors are connected channel Arr s...

Page 9: ...rating hours of the respective relay h P Full hours are shown on the display The operating hours added up can be reset As soon as one operating hours channel is selected the symbol in permanently show...

Page 10: ...note Switch on temperature difference DO must be at least 2 Ra higher than the switch off tempe rature difference DF DT O Switch on temperature Adjustment range 2 0 40 0 Ra Factory setting 12 0 DT F...

Page 11: ...OFF ON Factory setting OFF The minimum collector temperature is a minimum switching temperature which must be exceeded so that the solar pump R1 R2 is switched on The minimum temperature shall avoid a...

Page 12: ...sed for use of surplus energy or an after heating AH O AH F the thermostat function is used for after heating AH O AH F the thermostat function is used for use of surplus energy On the display is show...

Page 13: ...47 86 1117 203 1366 95 1136 212 1385 104 1155 221 1404 113 1175 230 1423 122 1194 239 1442 Resistance values of the Pt1000 sensors Check the power supply o k The can fuse of the controller is defectiv...

Page 14: ...fication no Heat exchanger plugged yes no Cleaning Heat exchanger too small yes New calculation of the dimension no Plausibility control of the option tube collector spe cial function Change Ton and T...

Page 15: ...up in manual operation yes There is no current check fuses replace them and check power supply The adjusted tempe rature difference for starting the pump is too high choose a matching setting no Is t...

Page 16: ...tening Sensors Our product range includes high precision platin temperatu re sensors flatscrew sensors ambient temperature sensors indoor temperature sensors cylindrical clip on sensors and irradiatio...

Reviews: