4.1.14 Tube collector special function
If the controller measures an increase of 4 °Ra compared
to the collector temperature tankd at last, the solar
pump is switched-on to 100 % for about 30 seconds.
After expiration of the solar pump runtime the current
collector temperature is tankd as new reference value. If
the measured temperature (new reference value) is again
exceeded by 4 °Ra, the solar pump again switches-on for 30
seconds. If the switch-on difference between collector and
tank is again exceeded during runtime of the solar pump
or the standstil of the system, the controller automatically
switches over to solar charging.
If the collector temperature drops by 4 °Ra during standstill,
the switch-on value for the special tube collector function
will be recalculated.
O TC:
Tube collector special
function
Adjustment range:
OFF ... ON
Factory setting: OFF
The thermostat function works independently from the solar
operation and can e.g. be used for use of surplus energy or
an after-heating.
•
AH O < AH F
the thermostat function is used for after-heating
•
AH O > AH F
the thermostat function is used for use of surplus
energy
On the display is shown
if the second relay output is
activated.
4.1.15 Thermostat function
(Arr = 2)
after-heating
use of surpluse energy
AH O:
Thermostat-switch-on
tem perature
Adjustment range:
32 ... 203 °F
Factory setting: 104 °F
AH F:
Thermostat-switch-off tem-
pe rature
Adjustment range:
32 ... 203 °F
Factory setting: 113 °F
For control and service work the operating mode of the
controller can be manually adjusted by selecting the adjust-
ment value HAND, in which the following adjustments can
be made:
4.1.16 Operating mode
• HAND
Operating mode
OFF
:
relay off
(flashing) +
AUTO :
relay in automatic operation
ON
:
relay on
(flashing) +
HAND1,HAND2:
Operating mode
Adjustment range:
OFF, AUTO, ON
Factory setting: AUTO
4.1.17 Language
The menu language can be adjusted in this channel.
•
dE : German
• En : English
• It : Italiano
• Fr : French
LANG:
Adjustment of language
Adjustment range: dE, En, It
Factory setting: En
4.1.18 Unit
The menu unit can be adjusted:
• °FAH
• °CEL
UNIT:
Adjustment of unit
Adjustment range: FAH, °C
Factory setting: FAH