Tanks are cooled during the night.

Does collector circuit 
pump run during the 
night?

no

yes

Check the controller 
functions

Collector temperature is 
at night higher than ambi-
ent temperature.

no

yes

Check  the  return  flow 
preventer in feed flow and 
return flow with regard to 
the functional efficiency.

Is the tank insulation 
sufficient?

yes

no

Intensify the insulation.

Is the tank insulation clo-
se enough to the store?

yes

no

Replace or intensify the 
insulation.

Are the tank connections 
insulated?

yes

no

Insulate connections.

Warm water outflow 
upwards?

no

yes

Change connection and 
let the water flow side-
wards or through a siphon 
(bow  downwards);  less 
tank losses now?

Does warm water circu-
lation run for a very long 
time?

no

yes

Use the circulation pump         
with timer and switch-off 
thermostat (energy effi-
cient circulation)

The solar circuit pump does not work although the coll-
ector is obviously warmer than the tank.

Does the control LED 
flash?

yes

no

Does the pump start up 
in manual operation?

yes

There is no current; check 
fuses / replace them and 
check power supply.

The adjusted tempe rature 
difference for starting the 
pump is too high; choose 
a matching setting

no

Is the current of the 
pump released by the 
controller?

yes

Is the pump stuck?

Put the pump into operati-
on by means of a screwdri-
ver; is it passable now ?

Is the pump out of order? 
- replace if necessary

Are the fuses o.k.?

Controller seems to be 
defective - replace it.

no

yes

no

no

yes

Replace the fuses.

Switch-off the circulation 
pump  and  the  blocking 
valve for 1 night; less tank 
losses?

yes

no

Check the pumps of the 
after-heating circuit ac-
cording to nightly run and 
defect return flow preven-
ter; problem solved?

no

no

yes

o.k.

Control the return flow 
preventer in warm water 
circulation- o.k.

yes

no

Please also check further 
pumps which are connec-
ted to the solar tank.

The gravitation circu lation 
in the circulation line is 
too strong; insert a stron-
ger return flow pre venter 
or an electrical 2-way val-
ve behind the circulation 
pump; the 2-way valve is 
open  in  pump  operati-
on, other wise it is closed, 
conect pump and 2-way 
valve in parallel; activate 
the circulation again!

Cleaning or replacement.

a

a

b

b

Summary of Contents for iSolar 3

Page 1: ...Thanks for buying this product Read this manual carefully to get the best perfomance from this unit Mounting Connection Handling Fault localization Examples manual 49005100 49005100...

Page 2: ...micro films and the storage into electronic systems Editor CALEFFI NORTH AMERICA Inc Important notice We took a lot of care over the texts and drawings of this manual and to the best of our knowledge...

Page 3: ...4 F Size 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Display System screen for sys tems visualisation 16 segment display 7 segment display 8 symbols for system stat...

Page 4: ...lief supports and screws Depending on the version the controller is equipped with 2 relays to which the consumers e g pumps valves etc can be connected Relay 1 18 conductor R1 17 neutral conductor N 1...

Page 5: ...nsors and after heating The sensor S4 TRF can optionally be used for heat quantity balancing Arr 2 1 2 2 Allocation of clamps for system 2 Symbol Specification S1 collector sensor S2 tank sensor below...

Page 6: ...d for scrolling forward through the indication menu or to increase the adjustment values The backwards key 2 is accordingly used for the reverse function For adjustment of last indication channel keep...

Page 7: ...he flow direction or the current bre aking capacity are always shown Heating circuit Tank 1 and 2 with heat exchanger After heating with burner symbol Temperature sensor 2 2 3 System screen only syste...

Page 8: ...types of antifreeze Corresponding channel is only available if the option heat quantity measurement is deactivated OWMZ Please note S3 and S4 are only indicated if sensors are connected channel Arr s...

Page 9: ...rating hours of the respective relay h P Full hours are shown on the display The operating hours added up can be reset As soon as one operating hours channel is selected the symbol in permanently show...

Page 10: ...note Switch on temperature difference DO must be at least 2 Ra higher than the switch off tempe rature difference DF DT O Switch on temperature Adjustment range 2 0 40 0 Ra Factory setting 12 0 DT F...

Page 11: ...OFF ON Factory setting OFF The minimum collector temperature is a minimum switching temperature which must be exceeded so that the solar pump R1 R2 is switched on The minimum temperature shall avoid a...

Page 12: ...sed for use of surplus energy or an after heating AH O AH F the thermostat function is used for after heating AH O AH F the thermostat function is used for use of surplus energy On the display is show...

Page 13: ...47 86 1117 203 1366 95 1136 212 1385 104 1155 221 1404 113 1175 230 1423 122 1194 239 1442 Resistance values of the Pt1000 sensors Check the power supply o k The can fuse of the controller is defectiv...

Page 14: ...fication no Heat exchanger plugged yes no Cleaning Heat exchanger too small yes New calculation of the dimension no Plausibility control of the option tube collector spe cial function Change Ton and T...

Page 15: ...up in manual operation yes There is no current check fuses replace them and check power supply The adjusted tempe rature difference for starting the pump is too high choose a matching setting no Is t...

Page 16: ...tening Sensors Our product range includes high precision platin temperatu re sensors flatscrew sensors ambient temperature sensors indoor temperature sensors cylindrical clip on sensors and irradiatio...

Reviews: