EVERSKY
™
MS-CDF-019
–
Manufacturing Nr: 22
0001→
Version B
Update: 2022/06/14
67/70
XXIV.3.
Alarm status (read-only)
It is not possible to acknowledge alarms (class A and B) via communication.
Read
Write
Modbus
Register Type
Modbus
Address
Modbus
Variable
BACnet
Address
Details
Alarm presence
X
Input Status
30
bool
BV, 20030 0=no alarm / 1=at least one alarm is present
Supply air fan fault
X
Input Status
33
bool
BV, 20033 0=no alarm / 1=alarm presence
Extract air fan fault
X
Input Status
34
bool
BV, 20034 0=no alarm / 1=alarm presence
Supply / extract air filters fault
X
Input Status
38
bool
BV, 20038 0=no alarm / 1=alarm presence
Internal battery fault
X
Input Status
80
bool
BV, 20080 0=no alarm / 1=alarm presence
Electrical heating coil overheating
X
Input Status
55
bool
BV, 20055
0=no alarm / 1=alarm presence
Only for units with electrical heating coil
hot water heating coil frost protection
X
Input Status
40
bool
BV, 20040
0=no alarme / 1=alarm presence
Only for units with hot water heating coil
Fire mode active
X
Input Status
42
bool
BV, 20042 0=no alarm / 1=alarm presence