EVERSKY
™
MS-CDF-019
–
Manufacturing Nr: 22
0001→
Version B
Update: 2022/06/14
66/70
XXIV.2.
Setpoints setting (read/write)
Unit
Read
Write
Modbus
Scale Factor
Modbus
Factory value
Modbus
Register type
Modbus
Address
Modbus
Variable
BACnet
Address
Details
Operating mode setpoint
-
X
X
1
Modbus :
3
Bacnet :
4
Holding Register
368
short
MSV, 30368
Modbus :
0=stop 1=low speed 2=high speed 3=auto
BACnet :
1=stop 2=low speed 3=high speed 4=auto
Supply constant air temperature setpoint
°C
X
X
10
180
Holding Register
1
short
AV, 30001
Only for supply constant air temperature control
Extract constant air temperature setpoint
°C
X
X
10
210
Holding Register
18
short
AV, 30018
Only for extract constant air temperature control
Temperature setpoint at outdoor temp.=-20°C
°C
X
X
10
250
Holding Register
10
short
AV, 30010
Only for (supply or extract) air temperature control on outdoor temperature
Temperature setpoint at outdoor temp.=-15°C
°C
X
X
10
240
Holding Register
11
short
AV, 30011
Only for (supply or extract) air temperature control on outdoor temperature
Temperature setpoint at outdoor temp.=-10°C
°C
X
X
10
230
Holding Register
12
short
AV, 30012
Only for (supply or extract) air temperature control on outdoor temperature
Temperature setpoint at outdoor temp.=-5°C
°C
X
X
10
230
Holding Register
13
short
AV, 30013
Only for (supply or extract) air temperature control on outdoor temperature
Temperature setpoint at outdoor temp.=0°C
°C
X
X
10
220
Holding Register
14
short
AV, 30014
Only for (supply or extract) air temperature control on outdoor temperature
Temperature setpoint at outdoor temp.=+5°C
°C
X
X
10
200
Holding Register
16
short
AV, 30016
Only for (supply or extract) air temperature control on outdoor temperature
Temperature setpoint at outdoor temp.=+10°C
°C
X
X
10
180
Holding Register
16
short
AV, 30016
Only for (supply or extract) air temperature control on outdoor temperature
Temperature setpoint at outdoor temp.=+15°C
°C
X
X
10
180
Holding Register
17
short
AV, 30017
Only for (supply or extract) air temperature control on outdoor temperature
Supply air fan high speed setpoint
%
X
X
10
700
Holding Register
424
short
AV, 30424
Supply air fan low speed setpoint
%
X
X
10
500
Holding Register
425
short
AV, 30425
Extract air fan high speed setpoint
%
X
X
10
700
Holding Register
426
short
AV, 30426
Extract air fan low speed setpoint
%
X
X
10
500
Holding Register
427
short
AV, 30427
CO2 setpoint 1
ppm
X
X
10
800
Holding Register
465
short
AV, 30465
CO2 setpoint 2
ppm
X
X
10
1000
Holding Register
466
short
AV, 30466