background image

Dual Relay

and 

Dual SSd

output options are factory set. 

Note:

(when in initial configuration only)Hold 

✱ 

and 

▲ 

or 

▼ 

for 10 seconds to move

to or from output devices in shaded portion.

SP2 OPERATING MODES

(see page 6)

Function      

Options

[Factory settings] shown in brackets

SP2.A [nonE]   

dV.hi  dV.Lo  bAnd   FS.hi   FS.Lo  Cool

Main SP2 operating mode

SP2.b  [nonE]    

LtCh  hoLd   nLin

Subsidiary SP2 mode: latch/sequence

Non-linear cool proportional band

INPUT SELECTION AND RANGING

dI.SP [1]     0.1

Select display resolution: for display of process temperature, setpoint,

OFSt, Set.2, hi.SC,

LoSC

.

hi.SC 

sensor minimum [sensor maximum]

°C/°F
Set full scale

Lo.SC

[sensor minimum] sensor maximum

°C/ºF
Set scale minimum

(default 0°C or 32°F)

inPt 

Select input sensor  

[nonE]

(See 

SENSOR SELECTION

table, page 11)

unit  [nonE]  

°C   °F  bAr   Psi  Ph  rh SEt

Select °C/°F or process units

LEVEL 3

OUTPUT CONFIGURATION

Note: ‘

Read only’ after initial configuration. 

rSET ALL

full reset to factory settings required 

to change 

SP1.d  

subsequently.

SP1.d   [nonE]    rLY

SSd           rLY1   rLY2   SSd1

Select SP1 output device

SP2.d   [nonE]    SSd   rLY

rLY2   rLY1  SSd2

Read SP2 output device

(read only)

burn  

Sensor burn-out/break protection

Caution: 

Settings affect fail safe state.

SP1

SP2

[uP.SC]

Upscale

Upscale

dn.SC   

Downscale

Downscale

1u.2d      

Upscale

Downscale

1d.2u      

Downscale

Upscale

rEu.d  

Select output modes: Direct/Reverse

Caution:

Settings affect fail safe state.

SP1

SP2

[1r.2d]

Reverse

Direct

1d.2d

Direct

Direct

1r.2r

Reverse  

Reverse

1d.2r

Direct

Reverse

Select 

Reverse 

on SP1 for heating and 

Direct 

for

cooling applications.

rEu.L

Select SP1/2 LED indicator modes

SP1

SP2

[1n.2n]

Normal

Normal

1i.2n

Invert

Normal

1n.2i 

Normal          Invert

1i.2i 

Invert            Invert

SPAn  [0.0]     to ±25% sensor maximum

Sensor span adjust

For recalibrating to align readings with another instrument e.g. External Meter, data logger.
See Full Operating Manual (ADVANCED SETTINGS).

ZEro 

[0.0]     to ±25% sensor f/s

Zero sensor error 

(see Sensor span adjust above).

ChEK   [oFF]     on

Select control accuracy monitor

rEAD  

[

Var]      hi      Lo

Read control accuracy monitor

tECh  

[

Ct A]     CT b    Ct 1    Ct 2    Ct 3   Ct 4    oS 1    uS    oS 2

Read Autotune tuning cycle data 

(see Operating Manual)

UEr  

Software version number

rSET 

[nonE]     ALL

Resets all functions to factory settings
Caution:

This selection will lose all of the current settings.

8

English

LEVL 3

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for CAL 3300

Page 1: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Page 2: ...ature Controllers CAL 3300 9300 9400 Autotune Temperature Controllers E n g l i s h F r a n a i s D e u t s c h I t a l i a n o E s p a o l Artisan Technology Group Quality Instrumentation Guaranteed...

Page 3: ...xit program mode Press together for 3 seconds To scroll through functions Press or To change levels or options Press together or together To view setpoint Press To increase setpoint Press together To...

Page 4: ...SP2 mode nonE LtCH hold Lt ho nLin Display resolution 1 or 0 1 degree Set scale maxim um 0 0 Sensor max to sensor full scale Set scale minim um 0 0 Sensor min to sensor full scale Select input sensor...

Page 5: ...n 100 C Re tuning after a large setpoint change Tuning multi zone and or heat cool applications Notes DAC is not re adjusted by Tune at setpoint Proportional Cycle Time can be pre selected before runn...

Page 6: ...OTUNE is initiated select CYC t in Level 1 press and hold both and or buttons until indexing stops at preferred value then exit program to accept CYCLE TIME RECOMMENDATIONS PROGRAMMER RAMP SOAK This f...

Page 7: ...lternating with the process temperature during alarm condition Notes The alarm will be automatically reset when the temperature returns within the bnd 2 setting in Level 1 The annunciator may be disab...

Page 8: ...OFF mode oFSt 0 to C F SP1 offset manual reset 50 bAnd Applicable in proportional and ON OFF mode with integral disable Int t oFF SP LK oFF on Lock main setpoint Locks the setpoint preventing unauthor...

Page 9: ...vice read only burn Sensor burn out break protection Caution Settings affect fail safe state SP1 SP2 uP SC Upscale Upscale dn SC Downscale Downscale 1u 2d Upscale Downscale 1d 2u Downscale Upscale rEu...

Page 10: ...T 1 16 DIN 45 0mm 0 6 0 0 wide 45 0mm 0 6 0 0 high 1 32 DIN 45 0mm 0 6 0 wide 22 2mm 0 3 0 high Maximum panel thickness 9 5mm Minimum spacing 20mm vertical 10mm horizontal MOUNTING To mount a Controll...

Page 11: ...cifications EN61010 CSA 22 2 No 1010 1 92 Compliance shall not be impaired when fitted to the final installation Designed to offer a minimum of Basic Insulation only The body responsible for the insta...

Page 12: ...to 50mV Applicable to all inputs SM sensor maximum Calibration accuracy 0 25 SM 1 C Sampling frequency input 10Hz CJC 2 sec Common mode rejection Negligible effect up to 140dB 240V 50 60Hz Series mod...

Page 13: ...and materials for three 3 years from date of purchase 1 Should the unit malfunction return it to the factory If defective it will be repaired or replaced at no charge 2 There are no user servisable p...

Page 14: ...0 1462 436161 Fax 44 0 1462 451801 email support cal controls co uk http www cal controls com CAL Controls Inc 1580 S Milwaukee Avenue Libertyville IL 60048 USA Tel 847 680 7080 Fax 847 816 6852 33017...

Page 15: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Reviews: