TUNE OR TUNE AT SETPOINT PROGRAM

Enter program (

▲▼

) and from the display

tunE : oFF  

press and hold 

✱ 

and press 

▲ 

to

display  

tunE : on

or 

tunE : At.SP

Exit program mode (

▲▼

).

The 

TUNE

program will now start. The display will show 

tunE

as the process temperature

climbs to setpoint.

Note:

During tuning, the main setpoint (SP1) LED will flash.

When the 

TUNE

or 

TUNE AT SETPOINT 

program is complete the PID values are entered

automatically. The process temperature will rise to setpoint and control should be stable. If
not, this may be because optimum cycle time is not automatically implemented. To set the
cycle time see 

PROPORTIONAL CYCLE-TIME

.

PROPORTIONAL CYCLE-TIME

The choice of cycle-time is influenced by the external switching device or load. eg.
contactor, SSR, valve. A setting that is too long for the process will cause oscillation and a
setting that is too short will cause unnecessary wear to an electro-mechanical switching
device.

Factory set

To use the 20 sec factory set cycle-time no action is needed whether autotune is used or
not. 

To Manually Select AUTOTUNE Calculated CYCLE-TIME

When AUTOTUNE is completed, enter program (

▲▼

) and select 

CYC.t

in 

Level 1

. The

display will read 

CYC.t : 20 

(the factory setting).

To view the new calculated optimum value, press and hold both 

✱ 

and 

▼ 

buttons until

indexing stops. The calculated value will be displayed eg.

A16

. If acceptable, exit program

(

▲▼

) to implement this setting.

To Pre-select Automatic Acceptance of AUTOTUNE Calculated CYCLE-TIME

Before AUTOTUNE is initiated select 

CYC.t

in 

Level1

, press and hold both 

and 

buttons

until indexing stops at 

A – –

. Exit program (

▲▼

) to accept calculated value automatically.

To Manually Pre-select Preferred CYCLE-TIME

Before AUTOTUNE is initiated select 

CYC.t 

in 

Level 1

, press and hold both 

and  

▲ 

or 

buttons until indexing stops at preferred value then exit program (

▲▼

) to accept.

CYCLE-TIME RECOMMENDATIONS

PROGRAMMER

RAMP-SOAK

This feature enables the controller to ramp up or down from current temperature to a
target setpoint at a pre-determined rate. It then controls at the target setpoint for an
adjustable soak period before switching off the SP1 output.

Set 

Setpoint ramp rate (

0 to 9995 deg/hour)

From

SPrr

in Level 1, press and hold 

and 

▲ 

or

to scroll to required ramp rate.

Set

Soak 

(if required) 0 to 1440 minutes

From 

SoAk

– – in Level 1, press and hold 

and 

▲ 

or

to scroll to required Soak time.

Set 

Ramp on

(Off: On: Hold)

From 

Sprn

in Level 1, press and hold 

, then press 

to select 

On

Exit program (

▲▼

) to enter settings into memory and commence ramp to target setpoint. 

Notes:

In 

Ramp on

configuration, if power is removed from the controller, the Ramp will

re-start when power is restored. 

The 

Ramp hold

option suspends the ramp at its last value.

If no 

Soak

period has been set, control at target setpoint continues indefinitely.

SP2 deviation alarms follow the ramp setpoint and can be used to alarm “out of
limits” ramp rate.

WARNING

The Soak timer is triggered when the ramp setpoint reaches the target setpoint. If the

ramp rate is set too fast for the process, the Soak timer will be triggered before the

process temperature reaches the target setpoint.

5

Output Device

Factory Setting

Recommended Minimum

Internal relay: rLY/rLY1/rLY2

20 seconds

20 seconds

10 seconds

Solid state drives: SSd/SSd1/SSd2

0.1 seconds

Target

setpoint

Deg.

Ramp 

°

/hour

Time

Soak

Target

setpoint

Deg.

Ramp 

°

/hour

Time

Soak

Hereafter in the Manual the symbol (

▲▼

) signifies both buttons are held pressed 

for 3 seconds to ENTER or EXIT Program mode.

English

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for CAL 3300

Page 1: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Page 2: ...ature Controllers CAL 3300 9300 9400 Autotune Temperature Controllers E n g l i s h F r a n a i s D e u t s c h I t a l i a n o E s p a o l Artisan Technology Group Quality Instrumentation Guaranteed...

Page 3: ...xit program mode Press together for 3 seconds To scroll through functions Press or To change levels or options Press together or together To view setpoint Press To increase setpoint Press together To...

Page 4: ...SP2 mode nonE LtCH hold Lt ho nLin Display resolution 1 or 0 1 degree Set scale maxim um 0 0 Sensor max to sensor full scale Set scale minim um 0 0 Sensor min to sensor full scale Select input sensor...

Page 5: ...n 100 C Re tuning after a large setpoint change Tuning multi zone and or heat cool applications Notes DAC is not re adjusted by Tune at setpoint Proportional Cycle Time can be pre selected before runn...

Page 6: ...OTUNE is initiated select CYC t in Level 1 press and hold both and or buttons until indexing stops at preferred value then exit program to accept CYCLE TIME RECOMMENDATIONS PROGRAMMER RAMP SOAK This f...

Page 7: ...lternating with the process temperature during alarm condition Notes The alarm will be automatically reset when the temperature returns within the bnd 2 setting in Level 1 The annunciator may be disab...

Page 8: ...OFF mode oFSt 0 to C F SP1 offset manual reset 50 bAnd Applicable in proportional and ON OFF mode with integral disable Int t oFF SP LK oFF on Lock main setpoint Locks the setpoint preventing unauthor...

Page 9: ...vice read only burn Sensor burn out break protection Caution Settings affect fail safe state SP1 SP2 uP SC Upscale Upscale dn SC Downscale Downscale 1u 2d Upscale Downscale 1d 2u Downscale Upscale rEu...

Page 10: ...T 1 16 DIN 45 0mm 0 6 0 0 wide 45 0mm 0 6 0 0 high 1 32 DIN 45 0mm 0 6 0 wide 22 2mm 0 3 0 high Maximum panel thickness 9 5mm Minimum spacing 20mm vertical 10mm horizontal MOUNTING To mount a Controll...

Page 11: ...cifications EN61010 CSA 22 2 No 1010 1 92 Compliance shall not be impaired when fitted to the final installation Designed to offer a minimum of Basic Insulation only The body responsible for the insta...

Page 12: ...to 50mV Applicable to all inputs SM sensor maximum Calibration accuracy 0 25 SM 1 C Sampling frequency input 10Hz CJC 2 sec Common mode rejection Negligible effect up to 140dB 240V 50 60Hz Series mod...

Page 13: ...and materials for three 3 years from date of purchase 1 Should the unit malfunction return it to the factory If defective it will be repaired or replaced at no charge 2 There are no user servisable p...

Page 14: ...0 1462 436161 Fax 44 0 1462 451801 email support cal controls co uk http www cal controls com CAL Controls Inc 1580 S Milwaukee Avenue Libertyville IL 60048 USA Tel 847 680 7080 Fax 847 816 6852 33017...

Page 15: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Reviews: