Stufe a pellet
8
Below 15 kW:
Air duct diameter
Maximum length (smooth duct)
Maximum length (corrugated duct)
50 mm
2 m
1 m
60 mm
3 m
2 m
80 mm
7 m
4 m
100 mm
12 m
9 m
Above 15 kW:
Air duct diameter
Maximum length (smooth duct)
Maximum length (corrugated duct)
50 mm
-
-
60 mm
1 m
-
80 mm
3 m
1 m
100 mm
7 m
4 m
Fig. 7 - Direct air inflow
Fig. 8 - Air inlet for sealed-chamber installation
LEGEND
1
Room to ventilate
2
External air inlet
4
Shield grid
5
Curve inlet to turn downwards
4.2
COMBUSTIBLE AIR INLET FOR SEALED-CHAMBER INSTALLATION
How to connect to the stove in the sealed chamber with concentric system:
Fig. 9 - Phase1
• Connect the air intake pipe to the combustion air pipe of the stove and tighten everything with a clamp (see [