11.17 POWER OUTPUT
Once the start-up stage is complete the control panel will display ON with a fixed flame at level 3. The subsequent flame modula-
tion at lower or higher powers is managed autonomously and upon reaching the temperatures set in the “System configuration”.
12 SAFETY DEVICES AND ALARMS
12.1 SAFETY DEVICES
The product is supplied with the following safety devices
12.2 PRESSURE SWITCH
Monitors pressure in the smoke duct. It is designed to shut down the pellets feed screw in the event of an obstructed flue or signi-
ficant back-pressure. (wind)
12.3 SMOKE TEMPERATURE PROBE
Detects the temperature of the smoke, thereby enabling start-up or stopping the product when the temperature drops below the
preset value.
12.4 CONTACT THERMOSTAT IN THE FUEL HOPPER
If the temperature exceeds the preset safety level, it immediately shuts down boiler operation.
12.5 CONTACT THERMOSTAT IN THE BOILER
If the temperature exceeds the preset safety level, it immediately shuts down boiler operation.
12.6 WATER TEMPERATURE PROBE
If the water temperature approaches the shutdown temperature (85°C) the probe makes the boiler perform the “OFF Stand-by”
automatic shutdown.
12.7 ELECTRICAL SAFETY
The product is protected against sudden current surges by a main fuse in the power supply panel on the rear part of the product.
Other fuses that protect the electronic boards are found on the latter.
12.8 SMOKE FAN
If the fan stops, the electronic board promptly shuts off the pellets supply and an alarm message is displayed.
12.9 GEAR MOTOR
If the gear motor stops, the boiler will continue to run until the flame goes out due to lack of fuel and until a minimum level of
cooling is reached.
12.10 TEMPORARY POWER CUT
If the power cut lasts less than 10” the boiler returns to its previous operating status; if it lasts more it carries out a cooling/restart
cycle.