background image

20

• Room used for supplying combustion air should be 

isolated from any area served by exhaust fans. 

• Refer back to the section on Fresh Air For Combustion 

for additional sizing guidelines.

Draft Regulators:

 Barometric draft regulator is required 

for controlling draft through boiler. Mount barometric draft 

regulator in chimney connector. Refer back to section on 

“Chimney And Chimney Connections”. Once draft regulator 

is installed, use draft gauge to adjust to proper opening: 

A.  Combustion chamber over 

fi

 re draft will be 

approximately -0.01” WC to -0.02” WC.

B.  Stack draft will be approximately -0.02” WC. to 

-0.04” WC. 

C.  Larger installation, greater draft will be required in 

stack to obtain desired over 

fi

 re draft.

Start:

 Fill entire system with water. Vent all air from 

system following section for Filling The Boiler.

Fuel Units And Oil Lines

:

 

• Install oil line(s) to oil burner.
• Recommend using heavy wall copper tubing and 

fl

 ared 

fi

 ttings, not compression 

fi

 ttings. 

• All connections and joints must be absolutely airtight. 

Use an appropriate non-hardening thread sealing 

compound on the threaded connections, not Te

fl

 on 

tape. 

• See fuel unit data sheet furnished with the burner for 

sizing, lift, and length of tubing recommendations.

Oil burner is equipped with single stage fuel unit 

with bypass plug removed for single pipe installation. 

Satisfactory where fuel supply is on same level as or 

above burner permitting gravity 

fl

 ow of oil. Per NFPA 31 

requirements, never exceed 3 psig pressure to inlet side of 

fuel unit. 

When necessary to lift oil to burner, two pipe installation 

is required. Run return line between fuel unit and oil 

supply. When two pipe installation is used, bypass plug 

(furnished with burner) must be installed in fuel unit. Refer 

to fuel unit instructions furnished with burner for speci

fi

 c 

instructions on installing bypass plug. Do not exceed fuel 

unit manufacturer’s recommendations for running vacuum. 

 

NOTICE

If lift exceeds 14 feet for Beckett burners or 11 feet 

for Riello burners, two stage fuel unit is required 

with return line.

Install oil 

fi

 lter of adequate size inside building between 

tank shutoff valve and oil burner. For ease of servicing, 

locate shutoff valve and 

fi

 lter near oil burner.

Air Supply For Combustion:

 

• Do not install boiler in rooms with insuf

fi

 cient air, unless 

corrective steps are taken. 

• It may be necessary to install windows or cut holes in 

a door to rooms used for supply air to obtain suf

fi

 cient 

combustion air and prevent less than atmospheric air 

pressure in that room. 

• If there is a lack of combustion air, burner 

fl

 ame will be 

dark orange and formation of soot will occur in heating 

unit. 

• In buildings of conventional frame, brick, or stone 

construction that do not have utility rooms, basement 

windows, or stair doors, air in

fi

 ltration is normally 

adequate to provide enough air for combustion and for 

operation of barometric draft control. 

OPERATING THE BOILER  

Nozzles And Electrodes

:

 Use proper size, spray angle, 

and spray pattern nozzle. Refer to recommended nozzle 

selection charts. 

To install nozzle, remove nozzle line electrode assembly, 

if necessary remove retention ring assembly, and install 

and tighten nozzle. Take care not to damage electrode 

insulators or bend electrode tips. 

After installing nozzle, reassemble nozzle line electrode 

assembly and set electrode tip spacing. 

Depending on burner type, electrode tip spacing may 

need to be set prior to reassembling nozzle line electrode 

assembly. 

Refer to following pages for setting electrode tip spacing.

Refer to Oil Burner Speci

fi

 cations chart for proper pump 

pressure and head adjustment.

Summary of Contents for BW4BAH-91

Page 1: ...0 BW4RAH 140 BW5BAH 140 BW5RAH 140 BW4BAH 126 BW4RAH 126 BW5BAH 126 BW5RAH 126 BW4BAH 175 BW5RAH 175 BW5BAH 175 BW5RAH 175 BW4BAH 210 BW4RAH 210 BW5BAH 210 BW5RAH 210 Models Series C BW4BAH 168 BW4RAH...

Page 2: ...fety relief valve drain valve flue brush and extra boiler tap for expansion tank or air elimination SAFETY NOTICES Boiler installation shall be completed by qualified agency NOTICE Used to address pra...

Page 3: ...183 84 3 5 13 7 21 6 11 Mbh 1 000 BTU per hour BTU British Thermal Unit Heating Capacity based on 13 CO2 with a 0 02 w c draft over fire and a 1 smoke or less Testing was done in accordance with the...

Page 4: ...es of steam and hot water which may damage the surroundings Before installing the safety relief valve read the manufacturer s instructions and maintenance section of the manual on safety relief valves...

Page 5: ...where passage is required for access to another side for cleaning servicing inspection or replacement of any parts that normally may require such attention Boilers must be installed at least 6 from co...

Page 6: ...IRCULATING PUMP IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED SAFETY SWITCH 2 FILL...

Page 7: ...ts the criteria for unconfined space Total input of all combustion equipment installed in combined space shall be considered in making this determination Each opening shall have minimum free area of o...

Page 8: ...he enclosure 3 When communicating with outdoors through horizontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of all equipment in t...

Page 9: ...ler See figure 6a A Install safety relief valve with spindle in vertical position B Do not install shutoff valve between boiler and safety relief valve C Install discharge piping from safety relief va...

Page 10: ...emperatures of less than 120 F Condensation is corrosive and can eventually cause damage to boiler and venting system Minimum design return water temperature to prevent this condensation in boiler and...

Page 11: ...M EXPANSION TANK NOTE CIRCULATORCANALSOBEINSTALLED ON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1...

Page 12: ...MPS AWAY FROM EXPANSION TANK PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure 9 System Piping Ar...

Page 13: ...ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATORS SYSTEM PIPING Fig...

Page 14: ...ine controls are used Tankless coils are meant to provide domestic hot water for intermittent draws not continuous flow NOTICE Do not use tankless coil if your water is excessively hard with lime or o...

Page 15: ...mption Tankless coil performance will fall as concentration of antifreeze is increased Refer to boiler and piping water volumes tables BOILER WATER VOLUMES Number of Boiler Section Total Volume Gallon...

Page 16: ...SIZES FIRING RATE gph CHIMNEY HEIGHT ft NOMINAL CHIMNEY ROUND LINER INSIDE SQUARE LINER INSIDE 0 60 1 30 15 8 x 8 6 6 x 6 1 31 1 80 15 8 x 8 7 6 x 6 1 81 2 00 20 8 x 8 8 6 x 6 For elevations above 2 0...

Page 17: ...Connection Minimum height Must be at least 3ft 9m higher than highest part of passage through roof Must be at least 2ft 7m higher than any neighboring object within 10ft 3m Must have unobstructed top...

Page 18: ...regulations Connect 115 volt electrical supply to L1 and L2 terminals on limit and two thermostat wires to T and T terminals on same limit See wiring diagram page 28 Run separate circuit from separate...

Page 19: ...ing drain valve runs air free close isolation valve or zone valve Repeat this procedure for remaining heating zones D Once all zones are filled with water and purged of air close power purging drain v...

Page 20: ...r must be installed in fuel unit Refer to fuel unit instructions furnished with burner for specific instructions on installing bypass plug Do not exceed fuel unit manufacturer s recommendations for ru...

Page 21: ...175 1 00 80 A 1 25 F6 1 NO 10 0 3 AFG F HEAD 140 BW 4 5 BAH 210 1 25 80 A 1 50 F6 1 NO 10 2 3 AFG F HEAD 140 BW 4 5 BAH 168 1 00 60 B 1 20 0 NO 10 1 5 2 AFG 50 MD 140 BW 4 5 BAH 245 1 50 45 B 1 75 2...

Page 22: ...22 OPERATING THE BOILER Figure 13 Burner Adjustments and Settings...

Page 23: ...e unit is full of vapor or when the combustion chamber is very hot Locate thermostat five feet above the floor on inside wall Locate thermostat to sense average room temperature avoid the following TH...

Page 24: ...ent that may lodge on valve seat Permit valve to snap shut Refer to valve manufacturer s instructions packaged for more details Conventional Expansion Tank Tank may become water logged or may receive...

Page 25: ...tions from combustion chamber area take care to not damage any of refractory or blanket insulation To gain access to combustion chamber first check that shut off valve on fuel oil line is closed and d...

Page 26: ...assembly make sure head location and size if applicable are per manufacturer s recommendations If burner being used has damaged head replace head with same head recommended for use on this boiler 6 In...

Page 27: ...k to be sure electric power supply circuit is ON Controls out of adjustment Reset according to instructions Radiators not heating Open radiator vents to excess air Check flow control valve if used It...

Page 28: ...28 ELECTRICAL WIRING Figure 16 Honeywell L7248L Control With Beckett AFG Burner...

Page 29: ...29 Figure 17 Honeywell L7248L Control With Riello F5 F10 Burner ELECTRICAL WIRING...

Page 30: ...burner fan motor to pre purge combustion chamber and oil pump to bring supply oil pressure up to its set point helping to provide clean light off LIMIT CONTROL provided Refer to manufacturer instructi...

Page 31: ...NOTES...

Page 32: ...CAC BDP 7310 West Morris St Indianapolis IN 46231...

Reviews: