background image

USER RESPONSIBILITIES

BS5839-1  is  the  British  Standard  code  of  practice  for  the  design,  installation,  commissioning  and
maintenance  of  fire  detection  and  fire  alarm  systems  for  buildings.  Section  7  of  the  standard  (User
Responsibilities) states that a named responsible person should be appointed to supervise all matters
pertaining to the fire alarm system {clause 47.2a}.

Highlighted below is a summary of the main functions the responsible person is expected to carry out
with regard to BS5839-1 only. It does not highlight any other responsibilities that may be required of
the user or responsible person that are listed in documentation such as the Employers Guide to Fire
Safety,  the  Fire  Precautions  (Workplace)  regulations  and/or  any  other  legislation  relevant  to  the
premises.  If  in  doubt,  the  fire  authority  can  advise  on  the  fire  legislation  that  applies  to  any  given
building. For countries outside the UK, different user responsibilities may apply.

BS5839-1 states the responsible person should: 

(The bracketed numbers {xx} identify the BS5839-1 clauses to which the summary refers.)

Ensure the fire alarm panel is checked daily to confirm there are no faults on the system {47.2b}

Ensure  arrangements  are  in  place  for  the  test,  maintenance  and  regular  servicing  of  the  system  with
regard  to  Section  6  of  the  standard  {47.2c}.  Important:  Clause  44  of  BS5839-1  recommends  weekly  and
monthly tests that should be carried out by the responsible person. See below for details.

Ensure the Fire Alarm Log Book is kept up to date by recording fire signals, fault signals, work on the
system, etc., and make sure it is available for inspection at all times {47.2d / 48}

Ensure all relevant occupants of the premises are instructed in the proper use of the system {47.2e}

Take steps to limit the number of false alarms on the system {47f}

Ensure the effectiveness of the system is not impaired by ensuring there is a space of at least 500mm in all
directions around and below every fire detector and that all manual call points are unobstructed and easy
to see {47g}

Liaise with all relevant building engineers, decorators, etc., to ensure any changes to (or maintenance of),
the building’s fabric does not compromise the protection given by the fire alarm system, create faults or false
alarms {47h}

Ensure that any structural or occupancy changes planned for the building are done so with due and early
consideration given to any changes that may be required to the fire system {47h}

Ensure that a selection of spare parts are held as appropriate within the premises {47j}

Routine weekly and monthly testing to be undertaken by the user/responsible person

To meet the requirements of Clause 44 of BS5839-1 we recommend the following tests are carried out at
approximately the same time each week, during normal working hours:

Note: It is essential any alarm receiving centre is contacted before and after these tests to avoid unwanted
alarms and to confirm the fire signal is correctly received.

• Carry out an Indicator lamp test to check all zone lights show and the beeper sounds.

• Operate a manual call point or smoke/heat detector to test the fire alarm.

• Check that the alarm sounders operate.

• Reset the system by pressing the Silence/Resound Sounders button and Control Panel Reset button.

• Verify that no manual call points or smoke/heat detectors are obstructed in any way.

• Test a different zone each week using a different call point or detector so all are tested in rotation.

Monthly attention: Ensure authorised service personnel verify the system’s standby power supply (or supplies)
are in good working order.

Quarterly and periodic inspection, testing, servicing and maintenance

It  is  the  user’s  responsibility  to  ensure  that  an  ongoing  periodic  plan  is  in  place  that  meets  Clause  45
(Inspection and Maintenance) of BS5839-1. The work required to meet this Clause must be carried out by a
competent person with specialist knowledge of fire detection and alarm systems. The standard recognises
this will normally be an outside specialist fire alarm servicing organisation.

Please note: the above summaries do not replace Sections 6 and 7 of BS5839-1 but are intended to help the user gain a greater understanding
of his or her responsibilities. We strongly recommend the named responsible person familiarises themselves with the full standard, copies of
which are available from your local reference library or can be purchased from the British Standards Institute, Customer Services Dept., 389
Chiswick High Road, London, W4 4AL. Tel: +44 (0)20 8996 9001. Web: www.bsi-global.com

XFP USER MANUAL & LOG BOOK • Approved Document No. DFU2000510 Rev 1 • Page 5 of 28

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

Summary of Contents for XFP

Page 1: ...XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL user manual and log book Approved Document No DFU2000510 Rev 1...

Page 2: ...t conditions 11 Access level 1 general user controls and menu options 12 Displaying fire fault disablement and test events 12 13 Testing the panel s lamps 13 Displaying the panel s alarm counter 13 Ac...

Page 3: ...the contents of the panel s separate engineering manual and have the necessary skills for maintaining this equipment If the enclosure is damaged in any way expert advice should be sought regarding it...

Page 4: ...to change the time the system enters day building occupied and night building unoccupied mode and to test the panel s indicators and liquid crystal display to ensure they are working correctly All of...

Page 5: ...tem create faults or false alarms 47h 8 Ensure that any structural or occupancy changes planned for the building are done so with due and early consideration given to any changes that may be required...

Page 6: ...vacuation general disablement test sounder status power supply fault general fault system fault delays running supply present more information escape accept 10 59 03 24 Jun Normal FREDCO WAREHOUSING F...

Page 7: ...sounder disablement anywhere on the system Delays Running Lit yellow when one or more output delays have been programmed into the panel Flashes yellow when one or more output delay is running Button c...

Page 8: ...r output units will not trigger in the event of a fire alarm condition for a set period of time as programmed by the system engineer Pressing the More Information button in a fire alarm condition will...

Page 9: ...but all previous zones will now appear on a step by step basis with details of which order they went into fire i e 1st zone 2nd zone etc Pressing the More Information button at any time will give you...

Page 10: ...tage alarm is in a zone set up with an investigation delay period Press the More Information button to display the actual device that has triggered the 1st stage fire condition pressing More Informati...

Page 11: ...panel s 5or6 buttons Press the More Information button to view additional details about the displayed fault For device specific faults the actual device that has triggered the fault condition will be...

Page 12: ...rised user engineer A record of any changes should appear on the System Set Up Data Chart on page 20 of this user manual If they do not contact your maintenance company for advice As soon as the code...

Page 13: ...etailed information if applicable can be viewed by pressing the panel s More Information button To return to the main access level 1 menu press the Escape3button Testing the Panel s Lamps This functio...

Page 14: ...keyswitch to the armed position I Silencing the alarm sounders To silence any active alarm sounders enter access level 2 see above and momentarily press the Silence Resound Sounders button The alarm s...

Page 15: ...nction displays the total number of times the panel has been in a fire alarm condition When selected press the Accept4button and the display will show the total number of times the panel has been in a...

Page 16: ...ill appear The DISPLAY EVENT HISTORY menu option when selected displays the panel s 500 event log on the display For example Initially only the last event will appear in the window but you can scroll...

Page 17: ...re re enabling the zone itself ENABLE DISABLE SOUNDERS This function allows you to disable one or more sounder groups from sounding in a fire condition When selected press the Accept4button and a wind...

Page 18: ...ss the Accept4button to select the desired option The window will now move to the next device allowing further enablements or disablements to be made Alternatively to return to the previous menu press...

Page 19: ...de by re entering it Enter the code again by pressing the 5 1 4 2 6 3 3 4 buttons in same sequence If the two codes match the panel will accept the code and you will be taken back to access level 2 If...

Page 20: ...nel is 3 3 3 3 four presses of the 6key If this code is changed make a note of the changes here New access level 2 code Date changed __________________ ADDITIONAL INFORMATION We recommend any addition...

Page 21: ...ll tests including fire drills Dates and times of all fires to which the system responds Dates and times of all false alarms Causes circumstances surrounding and category of false alarms if known The...

Page 22: ...ESSABLE FIRE ALARM PANEL Details of tests including fire drills actual fire alarms disablements or enablements and faults should be recorded here False alarms and maintenance work should be recorded o...

Page 23: ...AL LOG BOOK Approved Document No DFU2000510 Rev 1 Page 23 of 28 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPL...

Page 24: ...AL LOG BOOK Approved Document No DFU2000510 Rev 1 Page 24 of 28 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPL...

Page 25: ...AL LOG BOOK Approved Document No DFU2000510 Rev 1 Page 25 of 28 XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPL...

Page 26: ...NAL CAUSE IF KNOWN BRIEF CIRCUMSTANCES where cause is unknown record activities in the area MAINTENANCE VISIT REQUIRED YES or NO FINDINGS OF MAINTENANCE TECHNICIAN CATEGORY OF FALSE ALARM FURTHER ACTI...

Page 27: ...e as indicated by my our signatures below for the installation of the fire alarm system particulars of which are set out below CERTIFY that the said installation for which I we have been responsible c...

Page 28: ...ertificate Name in block letters Position in block letters Signature Date For and on behalf of Address postcode The extent of the liability of the signatory is limited to the system described below Ex...

Reviews: