ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 40 of 48
CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
TEST SOUNDERS IN GROUPS
This function allows you to test one, or all of the system’s sounder groups by altering their state between
Silenced, Intermittent and Continuous.
Enter AL3 (4444) > Engineer Functions > Test Sounders in Groups.
When the TEST SOUNDERS IN GROUPS prompt appears, press the Accept
4
button and the group
selection window will appear:
Press the
5
and
6
scroll buttons to select the sounder group you would like to test (1 to 16 or ALL).
Press the Accept
4
button and the following window will appear:
Press the Accept
4
button to change the state of the selected sounder group between Silenced,
Intermittent and Continuous. Should you want to test additional sounder groups, press the
5
and
6
buttons to change the sounder group’s number.
When exiting this function the panel will ask for confirmation to silence the sounders to their normal
settings. Press the Accept
4
button to reset the sounders, or the Escape
3
button maintain the settings.
Sounder Group : 1
Sounder Group : 1 is Silenced
Change the state using the Accept button
TEST OUTPUT SETS
This function allows you to test one, or all of the system’s output sets by altering their state from
Normal to Triggered.
Enter AL3 (4444) > Engineer Functions > Test Output Sets.
When the TEST OUTPUT SETS prompt appears, press the Accept
4
button and the output set selection
window will appear.
Press the
5
and
6
buttons to select the output set you would like to test (1 to 16 or ALL). Press the
Accept
4
button and the following window will appear:
Press the Accept
4
button and the selected output set will change state from normal to triggered.
To test additional output sets, press the
5
and
6
and Accept
4
button to change the output set’s
number and state.
Finally, press the Escape
3
button.
When exiting this function the panel will ask for confirmation to reset the outputs to their normal
settings. Press the Accept
4
button to reset the outputs, or the Escape
3
button maintain the settings.
Output Set : 1
Output Set : 1 is Normal
Change the state using the Accept button
Output Set : 1 is Triggered
Change the state using the Accept button