ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 15 of 48
CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
CONTROLS AND INDICATORS
Front panel layout
LED Indicators
Liquid Crystal Display
Provides detailed information on the status of the system (the type of messages
displayed and what they mean is covered in greater detail in the panel’s
separate user manual).
(General) Fire
Flashes red when there is a fire condition on any zone and goes steady red
when the alarm is silenced. Subsequent fire conditions will restart the (General)
Fire indicator flashing until it is silenced again.
Fire Zones (1-32)
One or more of these indicators will flash red in a zone alarm condition and
will go steady when silenced.
Supply Present
Normally lit green to show that all of the panel’s power supplies are
functioning correctly.
Test
Lit yellow when the panel is in walk test mode. This LED does NOT illuminate
for any other test condition.
Accessed
Lit yellow when the panel is in access levels 2 or 3.
General Disablement
Lit yellow when one or more zones, sounders, outputs, relays, devices, output
delays are disabled.
Phased Evacuation
Flashes yellow when there is a phased evacuation in progress.
Fire Zones
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16
Fire
general
fault
power supply
fault
system
fault
sounder
status
delays
running
test
accessed
general
disablement
phased
evacuation
more information
menu
silence
internal
sounder
silence/resound
sounders
control panel
reset
investigate
escape
accept
supply
present
10:59:03 24 Jun : Normal
FOXCO WAREHOUSING
General fault
Fire Alarm Control Panel Instructions
flashing light
- call engineer
O
I
To view more events use the scroll buttons
To silence the internal sounder
: press
To silence/resound the alarm sounders
: Turn key to
l
and press
OR
press and . Enter code and press
To reset the panel
: Ensure all alarm conditions are silenced
and investigations are complete and press
To exit access mode:
Remove key
OR
press and hold
The system must be tested regularly.
If in doubt, refer to the user manual.
EN54-2 & 4
Manufactured in England
XFP
176b