CAST XFP 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENGINEERING MANUAL • Approved Document No. DFU5010020 Rev 4 • Page 29 of 48
SHOW DUPLICATE ADDRESSES
This function helps to locate devices with duplicate (double) addresses by activating their device
(polling) LEDs.
If there is a duplicate address a fault may have been displayed at the panel stating, ‘Loop configuration
has changed on Loop 1’, ‘There are faults on this zone’.
Press More Information button, then press the
5
and
6
scroll buttons to view additional information
on the fault.
To show light the LEDs of the duplicate addresses enter:
AL3 (4444) > Commissioning Functions > Address Functions > Show Duplicate Addresses.
When the SHOW DUPLICATE DEVICES prompt is displayed press the Accept
4
button and details of the
double address will appear, for example:
Press the Accept
4
button and the LEDs of the devices with duplicate addresses will be lit steady red.
To fix the duplicate address at the panel, press the Escape
3
button and enter FIX DUPLICATE
ADDRESS function (see page 30).
To switch off the device LEDs, press the Accept
4
button again as shown below.
Loop: 1
Device 8 : Duplicate Address
Turn ON device LED?
Loop: 1
Device 8 : Duplicate Address
Turn OFF device LED?