F

Uzzy

 l

ogic

™  c

o

2 c

ontrol

 

(c

ontinUed

)

h

oW

 T

o

 p

erform

 “a

uTo

-T

uninG

”  

The Auto-Tuning function takes from 1 ½ to 2 ½ hours to complete. 

DON’T WORRY

. It is completely automatic once the test is started. 

However, before performing an Auto-Tuning, you 

MUST

 prepare the area for the procedure. This may take at the most 15 minutes.

1)  During the Auto-Tuning, the area must be operating normally. Circulating fans must remain operating.

2)  Exhaust and/or cooling fans which bring fresh air into the area must be disabled. If heat or humidity build-up is a problem during the  
 

2-hours required, reduce the lighting or other heat loads temporarily until the test is completed.

3)  Set the CO

2

 flow-gage to the setting most likely to be correct for your area. If no estimate is known, set it near the middle of the  

 

 

range and increase it if the first Auto-Tuning does not provide consistent control. 

4)  Turn the thermostat & humistat responsible for running the exhaust fans all the way to the maximum setting until the Auto-tune is    
 

complete.

5)  Close the CO

2

 tank valve. Connect the CO

2

 valve or generator to the XGC-1e. There should be no CO

2

 flowing out of the tank until    

 

the test is started. 

6)  Set the SV (desired CO

2

 level) to the desired level. (See Changing Set-Point) 

7)  Press [SEL] for 1 second. (RUN will be displayed)

8)  Press the [Down] button one time. (AT will be displayed)

9)  Press the [SEL] button once. (0 is displayed)

10)  Press the [UP or DOWN] button to bring up 1. (1 is displayed) 

11)   Press the [SEL] button once. The decimal point will begin to flash until the Auto-Tuning procedure is completed. The CO

2

 outlet will be 

energized. 

12)  Quickly open the CO

2

 tank valve and verify CO

2

 is flowing out of the flow-gage / regulator.

13)  Get out of the area and do not disturb the area for a minimum of 2 hours. After two hours, enter the area and confirm the decimal    
 

point has stopped flashing, which indicates the test is complete.

14)  Reconnect the Exhaust fans, CO

2

 Disable cable and return the area to normal operation while monitoring the level of CO

2

. Do not    

  

continue to stand next to the XGC-1e while monitoring. Just keep an eye on the display and record the level every 30 minutes or    

 

so. Also try to observe the unit reacting to and recovering from the Exhaust fans operating. The level should drop down to 800 or    

 

less and then recover quickly without overshooting the setpoint more than 150 PPM. 

15)  If after operating a day or two you are not getting good consistent control, (+/- 100 PPM from set point) it may be a good idea to    
 

perform a second Auto-Tuning. 

*NOTE: If your CO2 tank runs out for a period of time, the control may take a few hours to re-stabilize, this is normal.

c

hanGinG

 T

he

 s

eTpoinT

 (sv)

The XGC-1e has an adjustable set point. The set point is the minimum CO

2

 level in Parts-Per-Million you want to maintain. The face of the 

Fuzzy Logic controller has 5 led indicators on the front. The one marked (SV) is illuminated when viewing and / or changing the set point.

1)  Press (SEL) momentarily. The SV indicator will light up and the current set point is displayed.

       (The XGC-1e is factory set @ 1500 PPM) 

2)  Use the (UP / DOWN) buttons to change the set point to your desired level. Normally between 1250 –2000 PPM.

3)  Press the (SEL) button momentarily to accept the change.

c

hanGinG

 c

onTrol

 m

odes

People operating compressed CO

2

 systems will definitely benefit from the XGC-1e’s “Fuzzy Logic”. But some people who are using LP / 

Natural gas generators may want to extend the life of their generator by changing the XGC-1e’s control mode to ON / OFF. When operating 
in ON / OFF mode, the rapid pulsing of the control solenoid is eliminated. The XGC-1e will still control the CO

2

 generator with extreme 

accuracy. A preset hysteresis (dead-band) of 50PPM still allows the XGC-1e to control the CO

2

 to an average level of +/- 200 PPM. For 

comparison’s sake, the average accuracy of the Fuzzy Logic control mode is /-25PPM.  Follow the procedures listed below to 
easily change the control modes on the XGC-1e.

Summary of Contents for XGC-1e

Page 1: ...e maximum rating of the XGC 1e IMPORTANT Replace blown fuses with fuses of the same rating ONLY Note A surge suppressor power strip is always recommended when operating electrical equipment such as th...

Page 2: ...the best all in one controller available Humidity Controller Temperature Controller 2 Light Outlets 2 Hydro pump Outlets Hydro OFF timer Hydro mode selector switch Fuzzy Logic CO2 controller Fuse pro...

Page 3: ...ion of this manual Set the Hydro ON and OFF timers to your desired settings before continuing Refer to Timers 8 The 24 hour timeclock can now be set Push in the trip levers on the front face of the ti...

Page 4: ...levels The de humistat can control humidity levels from 20 80 The de humistat is coordinated with the CO2 control system and the exhaust receptacles to maintain a constant humidity When the humidity r...

Page 5: ...during the daytime only Simply moving the Hydro Mode selector switch to either the 24 Hour or the Daytime position enables the desired mode When used in the Daytime mode the Hydro outlet will only cyc...

Page 6: ...ssible However if you suspect the higher temperatures are adversely affecting the plants a shorter CO2 cycle may produce better results Remember that a shorter CO2 cycle duration translates to increas...

Page 7: ...is complete 14 Reconnect the Exhaust fans CO2 Disable cable and return the area to normal operation while monitoring the level of CO2 Do not continue to stand next to the XGC 1e while monitoring Just...

Page 8: ...XGC 1e is capable of remaining in calibration for a minimum of three years Extreme shock during shipping and other factors may affect the calibration To check the calibration follow the procedure bel...

Page 9: ...the HPR 1 The HPR 1 is rated at 30 amps 120 240 volt Master Lighting Controller Mlcs The MLC 4X and MLC 4XT Master Lighting Controllers are the best devices for controlling up to 4 HID lights from one...

Page 10: ...circuits If the fuse blows repeatedly verify the devices connected to the unit are working properly and that they are not too large for the XGC 1e to safely control You may need to consider using exp...

Page 11: ...00 PPM CO2 CO2 Warm up time Minimum 10 minutes full accuracy CO2 Maximum drift per year 15 PPM CO2 Accuracy 77 F 5 of reading CO2 Repeatability 1 of Fixed Scale CO2 Calibration interval Three years CO...