Field Name
Offset
Description
ID_H
0
Wireless device’s globally-unique identifier.
Combine a ID_H and ID_L to form full UInt32
number.
(READ-ONLY)
ID_L
1
VER_MAJOR
2
Wireless device’s firmware version number.
Registers VER_MAJOR::VER_MINOR to be
interpreted as ASCII characters with the
following format: “M0”.“M1”.“m0”.“m1”.
Example: VER = 0x3230::0x3136 → “Version:
2.0.1.6”.
(READ-ONLY)
VER_MINOR
3
TYPE
4
Device Type value that is used to interpret the
sensor specific portions of this record.
(READ-ONLY)
VOLTAGE
5
Current Voltage reported from the remote
device. Value formatted in millivolts.
(READ-ONLY)
.
Exampl
e: 301 → 3.01 Volts
RSSI
6
Current Received Signal Strength Indicator.
Formatted as Int16. Values of -20 to -106 dBm
typical. The less negative the number, the
more signal there was on the last
communication.
(READ-ONLY)
.
STATUS
7
Current Status reported from the remote
device.
(READ-ONLY)
.
DATA_0
8
The current data reported by the remote
device.
(READ-ONLY)
.
DATA_1
9
DATA_2
10
DATA_3
11
DATA_4
12
DATA_5
13
DATA_6
14
DATA_7
15
INACTIVITY_
TIMEOUT
16
Timeout in 5 min steps. Values of 1 to 216 (5
min to 18 hrs) permitted. If the device has
communicated within the amount of time
specified here, the ACTIVE coil is set to TRUE.
If No communications have occurred with the
devices for this specified amount of time, the
ACTIVE coil is reset to FALSE.
- 30 -