9

EN

Observe all applicable installation regulations, ge-

neral guidelines and technical specifications. Install 

the filter in the cold water pipes upstream of the ob-

jects to be protected. Always provide stop valves.

Caution: The installation site must be protected 

against frost and must guarantee the protection of 

the filter from solvent vapors, fuel oil, lees, chemi-

cals of all types, UV irradiation, and heat sources 

see tecnical data. The filters should be according 

to the nominal connection width in the same di-

mension fitted in the pipework. Install the filter in 

the direction of flow in the vertical or horizontal 

cold water pipe.

Caution: Keep plastic parts free of oil, grease, 

solvents and acid or alkaline cleaning agents. 

Avoid extreme pressure blows (closure-beat by 

downstream magnet valve e.g.).

5. Installation

See installation drawing.

Install the filter and the stop valves before and after 

the filter in flow direction in the water pipe (see 

flow direction arrows an top section).

Route the flushing water connection with hose to 

the sewage channel or provide a collection basin 

(capacity approx. 10 l). Please note: According to 

DIN EN 1988-200, the flushing water hose must be 

installed at a miniumum distance of 20 mm to the 

highest possible waste water level (free discharge).

6. Startup

Check the filter for correct and proper installation.

The shut-off valves must not be opened yet. Check 

the filter bottom part and rinsevalve to ensure cor-

rect fit. Close the rinsevalve. It should not used any 

tool. Maximum torque 8 - 10 Nm at recess  of plastic 

parts in brass parts. Slowly open the shut-off valves 

before and after the domestic waterstation and dea-

erate the piping at the next tapping point after the 

domestic water-station. Check the filter for leaks.

The pressure reducer is set to a back pressure of 

4 bar at the factory. To change the back pressure, 

loosen the locking screw (6) and turn the rotary 

knob (7). The back pressure can be changed by tur-

ning the setting knob (7) (control range 2 - 6 bar).

Clockwise rotation = higher back pressure.

Anti-clockwise = lower back pressure.

During setting, an outlet valve downstream from the 

pressure reducer must be briefly opened and closed 

again a number of times. When water is removed, 

the back pressure is temporarily reduced. The back 

pressure must not exceed 80 % of the response pres-

sure of the hot water safety valve (DIN 1988-200).

7. Operation

The filter must be checked at regular intervals, i.e. 

every two months (according to DIN 1988-200) 

and also must be rinsed. If there is a noticeable 

drop of the pressure, caused by increasing pollu-

tion of the filter cloth, the filterelement must be 

replaced. The filterelement must be replaced after 

6 months at the latest (according to DIN 1988-

200). Close the stop valves before and after the fil-

ter and provide a collecting basin under the filter. 

Open rinsevalve for pressure relief and empty the 

filter. Open the filter bottom part with tool (wrench 

width 21) or by hand. Clean the filter bottom part. 

Exchanging the filter element: 

Water is a consumable liquid. When exchanging the 

filter, proper hygiene must be ensured. The plastic 

parts may only be cleaned with a soft, damp cloth. 

Do not use any solvents or detergents nor acid 

cleaners. Remove the filterelement and exchanged 

against a new filterelement. Place the filterelement 

in the top section and screw it with the bottom part. 

Close the rinsevalve. Slowly open the stop valves, 

first those before, then those after the filter. Check 

the filter for proper sealing and then deaerate the 

pipe at the bleeding point closest tot he filter (af-

ter the filter).

8. Warranty

In the event of a failure during the warranty peri-

od, please contact your contractual partner, the 

plumbing company, stating the appliance type 

(see specifications and/or rating plate of the ap-

pliance).

> 20 mm

Summary of Contents for Protector mini HWS C/R

Page 1: ...u und Bedienungs anleitung stets griffbereit aufzubewahren vor der Ausf hrung von Arbeiten am Ger t vollst ndig durchzulesen und zu beachten Unsere Merkbl tter und Druck schriften sollen nach bestem W...

Page 2: ...ht haben Thank you very much for the con fidence that you have shown in us by purchasing a BWT appliance Nous vous remercions de votre confiance pour l achat d un appareil BWT Vi ringraziamo per la fi...

Page 3: ...4 2 1 Filtration 4 2 2 Druckminderer 4 3 Funktion 4 3 1 Filtration 4 3 2 Druckminderer 4 4 Einbauvorbedingungen 4 5 Einbau 5 6 Inbetriebnahme 5 7 Bedienung 5 8 Gew hrleistung 5 9 Betreiberpflichten 6...

Page 4: ...enn der Vordruck zwischen z B 16 bar und dem eingestellten Hinterdruck z B 3 bar schwankt Ein gleichm iger und nicht zu hoher Druck schont Armaturen und Ger te in der gesam ten Hauswasserinstallation...

Page 5: ...lschraube 6 l sen und den Drehknopf 7 verdrehen Der Hinterdruck l sst sich durch Drehen am Einstellknopf ver ndern Re gelbereich 2 6 bar Drehen im Uhrzeigersinn h herer Hinterdruck Drehen gegen den Uh...

Page 6: ...nal Nur Fachpersonal darf das Produkt installieren in Betrieb nehmen und Instand halten Die Bedienung und der Gebrauch hat durch unterwiesene Personen zu erfolgen Unterwiesene Person Wurde in einer Un...

Page 7: ...ltration 8 2 2 Pressure reducer 8 3 Function 8 3 1 Filtration 8 3 2 Pressure reducer 8 4 Installation conditions 8 5 Installation 9 6 Startup 9 7 Operation 9 8 Warranty 9 9 Operator responsibility 10...

Page 8: ...uctuates bet ween for example 16 bar and the set back pres sure e g 3 bar A uniform not too high pressure preserves fittings and devices in the entire dome stic water installation helps to save up to...

Page 9: ...ssure of 4 bar at the factory To change the back pressure loosen the locking screw 6 and turn the rotary knob 7 The back pressure can be changed by tur ning the setting knob 7 control range 2 6 bar Cl...

Page 10: ...erate and use it Trained person Has received instruction and stu died the information in this document concerning the tasks entrusted to him her and the possible risks in the event of inappropriate be...

Page 11: ...2 R ducteur de pression 12 3 Fonctionnement 12 3 1 Filtration 12 3 2 R ducteur de pression 12 4 Conditions de montage 12 5 Installation 13 6 Mise en service 13 7 Utilisation 13 8 Garantie 13 9 Obliga...

Page 12: ...e Une pression constante et mod r e prot ge la robi netterie et les appareils raccord s au r seau d eau Nous recommandons l installation d un r ducteur de pression partir de 4 bar en amont 3 Fonctionn...

Page 13: ...irement 7 Utilisation V rifier et rincer le filtre r guli rement tous les deux mois cf DIN 1988 200 En cas d encrassement progressif du tissu filtrant entra nant une baisse sensible de la pression d e...

Page 14: ...entuels risques susceptibles de survenir en cas de comportement inad quat Personnel technique Celui ci est en mesure d installer et de mettre en service le produit ainsi que d effectuer les travaux de...

Page 15: ...16 2 2 Riduttore di pressione 16 3 Funzionamento 16 3 1 Filtrazione 16 3 2 Riduttore di pressione 16 4 Premesse all installazione 16 5 Installazione 17 6 Messa in funzione 17 7 Utilizzo 17 8 Garanzia...

Page 16: ...e in uscita entro i valori impostati ad es 3 bar Una pressio ne costante e non eccessiva garantisce l efficienza della rubinetteria e delle apparecchiature di tutto l impianto idrico domestico consent...

Page 17: ...regolata ruot ando la manopola campo di regolazione 2 6 bar Rotazione in senso orario aumento della pressione in uscita Rotazione in senso antiorario diminuzione della pressione in uscita Durante la r...

Page 18: ...comando e l uso devono essere affidati a persone con appropriata for mazione Persona con appropriata formazione ha ricevuto un apposito insegnamento e una formazione effettuata in base alle informazi...

Page 19: ...20 2 1 Sz r s 20 2 2 Nyom scs kkent 20 3 M k d s 20 3 1 Sz r s 20 3 2 Nyom scs kkent 20 4 A be p t s el felt telei 20 5 Be p t s 21 6 zembe helyez s 21 7 Kezel s 21 8 J t ll s 21 9 Az zemeltet k tele...

Page 20: ...a be ll tott ellennyom s pld 3 bar k z tt ingadozik Az egyen letes s nem t l nagy nyom s k m li a szerelv ny eket s k sz l keket az eg sz h zi v zrendszerben ak r 50 vizet seg t megtakar tani s minim...

Page 21: ...s val lehet v ltoztatni szab lyoz si tartom ny 2 6 bar Az ramutat j r si ir ny ba forgatva nagyobb ellennyom s Az ramutat j r si ir ny val szembe forgatva ki sebb ellennyom s Az ellennyom sra megadott...

Page 22: ...yzet A term ket csak szaksze m lyzetnek szabad felszerelnie zembe helyeznie s karbantartania A term ket betan tott szem lyek kezelj k s haszn lj k Betan tott szem ly oktat s keret ben s ezen t mutat b...

Page 23: ...4 2 1 Filtrace 24 2 2 Reduk n ventil 24 3 Funkce 24 3 1 Filtrace 24 3 2 Reduk n ventil 24 4 P edb n podm nky pro mont 24 5 Mont 25 6 Uveden do provozu 25 7 Obsluha 25 8 Z ruka 25 9 Povinnosti provozov...

Page 24: ...st Doporu ujeme mont reduk n ho ventilu od vstupn ho tlaku 4 bary 3 Funkce 3 1 Filtrace Surov voda proud p es vstup do filtru a tam zven dovnit filtra n vlo kou k v stupu ist vody P itom jsou ciz stic...

Page 25: ...likr t kr tce otev en a zase zav en P i odb ru vody p echodn klesne v stupn tlak V stup n tlak nesm in v ce ne 80 otev rac ho tlaku bezpe nostn ho ventilu tepl vody DIN 1988 200 7 Obsluha Filtr v prav...

Page 26: ...byla v r mci kolen a informac z tohoto n vodu zpravena o j p id len ch loh ch a mo n ch nebezpe ch p i nespr vn m chov n Odborn person l Je schopn na z klad sv ho odborn ho vzd l n znalost a zku enost...

Page 27: ...ltracja 28 2 2 Reduktor ci nienia 28 3 Spos b dzia ania 28 3 1 Filtracja 28 3 2 Reduktor ci nienia 28 4 Wst pne warunki monta u 28 5 Monta 29 6 Uruchomienie 29 7 Eksploatacja 29 8 Gwarancja 29 9 Obowi...

Page 28: ...r i urz dzenia w ca ej domowej instalacji wodnej poma ga zaos zcz dzi do 50 wody i minimalizuje pow stawanie szum w Monta reduktora zalecamy przy ci nieniu wlotowym wynosz cym minimum 4 bary 3 Spos b...

Page 29: ...ie pokr t a nastawczego zakres regulacji 2 6 bar w Obracanie zgodnie z ruchem wskaz wek zegara wy sze ci nienie wyj ciowe Obracanie przeciwnie do ruchu wskaz wek zegara ni sze ci nienie wyj ciowe Wska...

Page 30: ...Manometr co 6 lat Wk ad reduktora ci nienia 11 co 6 lat ZgodniezDINEN806 5wymianacz cizu ywalnych musi by przeprowadzana przez wyspecjalizowa ny personel instalator lub autoryzowany serwis Zalecane je...

Page 31: ...31 RU 1 32 2 32 2 1 32 2 2 32 3 32 3 1 32 3 2 32 4 33 5 33 6 33 7 33 8 34 9 34 10 35...

Page 32: ...32 RU 1 Protector mini HWS C R 1 p 2 810599 3 810560 4 5 6 7 8 9 10 11 12 1 4 2 2 1 ProtectorminiHWS 2 2 16 3 50 3 3 1 30 100 1 6 3 2 7 8 6 7 8 9 10 11 3 2 5 1 H R C R 072843 4 Art Nr 333800 12...

Page 33: ...33 RU 4 AVB Wasser V 12 2 5 6 8 10 4 6 7 7 2 6 80 DIN 1988 200 7 1 2 DIN 1988 200 DIN 1988 200 21 H R...

Page 34: ...34 RU 8 9 DIN 1988 200 2 1 6 1 3 DIN EN 806 5...

Page 35: ...15 20 p 0 5 m 1 6 2 8 3 7 1 6 2 8 2 6 90 110 PN 16 10 min max 1 5 PN 16 min max C 5 30 5 70 min max C 5 40 A G G G 1 G G B G G 1 G 5 4 G G 1 C 80 90 100 80 90 D 170 170 170 170 170 E 130 154 180 130 1...

Page 36: ...224 500 Fax 33 1 49 224 5 5 E Mail bwt bwt fr BWT UK Limited BWT House The Gateway Centre Coronation Road High Wycombe Buckinghamshire HP12 3SU United Kingdom Phone 44 1494 838100 Fax 44 1494 838101...

Reviews: