7 | Input / Output Description
32 | 44
Pump Control Instructions INVEOR VFD R5 COBRA_EN_en
4.053 AI2 dead time (%)
Dead time as percentage of the range of the analogue input:
0 = no dead time default value, to be adapted to your process
4.054 AI2 filter time (second)
Filter time of analogue inputs in seconds:
0.02 = default value to be adapted to your process
4.060 AI2 function
Function of analogue input 2:
0 = analogue input
4.063 AI2 physical unit
Selection of different physical values to be displayed:
4.063 =
0
%
4.063 =
1
bar
4.063 =
2
mbar
4.063 =
3
psi
4.063 =
4
Pa
4.063 =
5
m
3
/h
4.063 =
6
l/min
4.063 =
7
°C
4.063 =
8
°F
4.063 =
9
m
4.063 =
10
mm
4.064 AI2 physical unit minimum
Selection of the lower limit of a physical value to be displayed:
0 = default value to be adapted to your process
4.065 AI2 physical unit maximum
Selection of the upper limit of a physical value to be displayed:
100 = default value to be adapted to your process
7.6.4.2
Current Input
1.100 Control mode
Selecting the operation mode, following software enabling (1.131) and hardware enabling, the drive
controller runs as follows:
0 = frequency control mode, with the target value of the selected reference channel 1.130
1.130 Reference channel
Determines the source from which the target value is to be read:
2 = analogue input 2
4.050 AI2 input type
Function of analogue input 2:
2 = current input
4.051 AI2 minimum input (%)
Specifies the minimum value of the analogue inputs as a percentage of the range:
Example:
0 … 20 mA
►
0% … 100%
4 … 20 mA
►
20% … 100%
0
►
0 mA
►
0% = default value to be adapted to your process