Input / Output Description | 7
Pump Control Instructions INVEOR VFD R5 COBRA_EN_en
29 | 44
0 = frequency control mode, with the target value of the selected reference channel 1.130
1.130 Reference channel
Determines the source from which the target value is to be read:
1 = analogue input 1
4.020 AI1 input type
Function of analogue input 1:
1 = voltage input
4.021 AI1 minimum input (%)
Specifies the minimum value of the analogue inputs as a percentage of the range:
Example:
0 … 10 V
►
0% … 100%
2 … 10 V
►
20% … 100%
0
►
0 V
►
0% = default value to be adapted to your process
4.022 AI1 maximum input (%)
Specifies the maximum value of the analogue inputs as a percentage of the range:
Example:
0 … 10 V
►
0% … 100%
2 … 10 V
►
20% … 100%
100
►
10 V
►
100% = default value to be adapted to your process
4.023 AI1 dead time (%)
Dead time as percentage of the range of the analogue input:
0 = no dead time default value to be adapted to your process
4.024 AI1 filter time (second)
Filter time of analogue inputs in seconds:
0.02 = default value to be adapted to your process
4.030 AI1 function
Function of analogue input 1:
0 = analogue input
4.033 AI1 physical unit
Selection of different physical values to be displayed:
4.033 =
0
%
4.033 =
1
bar
4.033 =
2
mbar
4.033 =
3
psi
4.033 =
4
Pa
4.033 =
5
m
3
/h
4.033 =
6
l/min
4.033 =
7
°C
4.033 =
8
°F
4.033 =
9
m
4.033 =
10
mm
4.034 AI1 physical unit minimum
Selection of the lower limit of a physical value to be displayed:
0 = default value to be adapted to your process