8
Supporting Floor Systems
It is the ultimate responsibility of the installer to ensure that
proper concrete slab supports are used.
WARNING
to the licensed design professional and/or building
contractor: It is your responsibility to be certain that the
Burntech® can be properly supported by the combustible floor
system on which the fireplace will rest.
For fireplace support foundations installed on concrete refer to
Appendix I and II (
pages 31 & 32
) for specific instructions.
Rebar locations
Lay-out the position of the fireplace and drill holes where
the rebar will be located. Secure the #3 rebar 4 inches into
the concrete foundation with ITW Epoxy or Simpson Epoxy.
Follow manufacturer’s instructions for installation of rebar into
slab.
Wood Floor
Anchorage of fireplace to wood floor construction is required.
Refer to
Figure 9
for anchorage dimensions. Four anchors are
required to attach to the sub-flooring framing.
Crawl Space or Upper Floor:
For installation of firebox over combustible crawl spaces or
upper floors, anchorage of the firebox is required. Illustrations
of examples of possible anchorage methods are shown in
Figures 6 thru 8 depending upon the type of floor framing. Final
method of anchorage is to be determined by licensed design
professional.
For conventional framing, where the floor joists are parallel
with the sides of the firebox, the addition of floor joists to align
with the anchor brackets allows the brackets to be directly
connected to the floor joists.
Note that additional floor joists may be required to support
the weight of the firebox and chimney. Where the floor joists
run parallel to the front of the firebox, anchorage can be
accomplished in like manner as shown in Figure 6 using
blocking between the floor joist.
For floors supported by I-Joists, the method of anchorage is
illustrated in Figures 7 and 8. Figure 11 illustrates the general
arrangement of anchorage to floor framing.
It is important to take into consideration that the load for
the Burntech® Fireplace must be considered as additional
dead load that will have to be supported by the floor framing.
Additional floor joists or I-joists may be required as determined
by the licensed design professional.
The dead weights for the fireplace are noted in Table I. It is
the task and responsibility of the general contractor/installer
to see that the proper reinforcement for weight loads are
made by a licensed design professional prior to the fireplace
installation.
As stated above, it is desirable to place additional framing
for alignment of anchor rods. Refer to Figure 9 for anchor rod
locations.
Figure 6
Floor Sheathing
not shown for
clarity
Metal Base
Assembly
EXAMPLE ONLY
2X FLOOR JOIST
2X FLOOR JOIST
A35 Brackets
(16 required)
I-Joist
Simpson
Strong-Tie
A-35 or
equivalent
Figure 7
I-Joist Anchoring
Top View
Example Only
I-JOISTS
Anchor
Brackets
Figure 8
I-Joist
Anchoring
Bottom
View
Example Only