Burnham V9 Series Manual Download Page 6

6

NOTES:
1.  All piping is schedule 40.
2.  Pipe sizes listed are based on a 20°F 

or

 40°F differential  

  (temperature drop). Select one to match application.   
  Consult factory if boilers are used in low temperature   
  applications or blending/mixing devices.

3.  When specified return piping size is less than 3”, install   
  3” X 12” nipple and appropriate size bell reducer directly 

   into boiler return tapping as shown.

4.  Drain valve — ball valve preferable, gate valve acceptable  

  alternative (supplied by others).

  - Minimum valve size per ASME code is 3/4” NPT
5.  For multiple water boiler piping, consult factory.

WATeR BOILeR pIpInG

To be used when system return water is not less

 than 135° F for prolonged periods of time and system flow 

does not impact flow through the boiler

MODeL

SUppLy pIpInG SIZe 

(In.) (1)

ReTURn pIpInG SIZe (In.)

ReTURn (2)

ReTURn 

HeADeR (2A)

ReTURn BRAnCH 

(QTy.) SIZe (2B)

20¡F D ROp

40¡F D ROp

20¡F 

DROp

40¡F 

DROp

20¡F D ROp

20¡F 

DROp

V903A

V904A

V905A

V906A

V907A

V908A

V909A

V910A

V911A

V912A

2

2

2

2-1/2

2-1/2

2-1/2

3

3

3

4

1-1/2

1-1/2

1-1/2

1-1/2

2

2

2

2-1/2

2-1/2

2-1/2

2

2

2

2-1/2

2-1/2

2-1/2

3

3

3

4

1-1/2

1-1/2

1-1/2

1-1/2

2

2

2

2-1/2

2-1/2

2-1/2

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

3

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

(2) 3

STeAM BOILeR pIpInG

nOTeS:

1.  All piping is schedule 40.

2.  To prevent condensate from being trapped in header, do not reduce  
 

equalizer elbow at header connection.

3.  Drain/blowoff valve — ball valve preferable, gate valve acceptable   

 

alternative (supplied by others).

 

– Minimum valve size per ASME code is 3/4” NPT 903A/905A; 

 

 

  1” NPT 906A/910A; 1-1/4” NPT 911A/912A.

 

Р  Increasing the valve size will improve the blowdown operation. 

 

Р  In all cases, piping connection blowoff valve to boiler should be  

  

full size to the point of discharge.

4.  For pumped return systems, see V9A installation manual.
5.  For multiple steam boiler piping, consult factory.

MODeL

pIpInG SIZe (In InCHeS)

RISeR SpACInG  

(InCHeS)

RISeR 

(Qty.) SIZe (1)

HeADeR & 

SUppLy (2)

ReTURn 

(3)

eQUALIZeR 

(4)

'A'

'B'

V903A

V904A

V905A

V906A

V907A

V908A

V909A

V910A

V911A

V912A

(1)  3

(1)  4

(1)  4

(1)  4

(2)  4

(2)  4

(2)  4

(2)  4

(2)  4

(3)  4

3

4

4

4

6

6

6

6

6

6

1-1/2

2

2

2-1/2

2-1/2

2-1/2

2-1/2

3

3

3

2

2

2

2-1/2

2-1/2

2-1/2

2-1/2

3

3

3

Ñ

Ñ

Ñ

Ñ

36

42

48

54

60

30

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

Ñ

36

V9 Series Piping Recommendations

Water and Steam

Summary of Contents for V9 Series

Page 1: ...or Steam Boiler 447 to 2367 MBH Input Oil Gas or Oil Gas Combination 30 50 or 80 PSI Cast Iron Sectional Design Water or Steam Top or Rear Venting Exclusive Optional SBC Boiler Control M aximizes Sys...

Page 2: ...gross output ratings from 347 to 1900 MBH the V9 Series fires gas oil or combination gas oil and is available equipped with either steam or water trim The product meets the energy efficiency requireme...

Page 3: ...ial America s Boiler Company has earned a reputation for quality and dependability Built for a variety of applications the V9 Series is right for your next job Individual Draw Rods with reinforced lug...

Page 4: ...tability Easily integrated into existing or new building management systems Simplified connections available to most building management systems through Modbus or standard 0 10 volt signals Uses sophi...

Page 5: ...JB G H V903A 3 18 1 4 12 1 9 1 8 1 7 8 9 3 4 8 20 7 8 8 23 1 4 8 20 1 8 908 1278 V904A 4 24 1 4 18 1 12 1 8 1 7 8 11 3 4 8 21 5 8 8 23 1 4 8 20 1 8 8 30 1194 1590 V905A 5 30 1 4 24 1 15 1 8 1 8 8 11 3...

Page 6: ...A V912A 2 2 2 2 1 2 2 1 2 2 1 2 3 3 3 4 1 1 2 1 1 2 1 1 2 1 1 2 2 2 2 2 1 2 2 1 2 2 1 2 2 2 2 2 1 2 2 1 2 2 1 2 3 3 3 4 1 1 2 1 1 2 1 1 2 1 1 2 2 2 2 2 1 2 2 1 2 2 1 2 3 2 3 STeAM BOILeR pIpInG nOTeS...

Page 7: ...URe InCHeS V903A V904A V905A V906A V907A V908A V909A V910A V911A V912A CG10 1S CG10 4S CG10 5S CG10 6S CG15 3S CG15 4S CG25 2S CG25 3S CG25 4S CG50 2S 1 3 1 3 1 3 1 3 1 2 1 2 3 4 3 4 3 4 2 3 3 3 7 4 7...

Page 8: ...gas valves gas electric ignition with proven gas pilot flame rod on JR burner ultra violet flame detector on others electronic programming controls and components are factory wired in a burner mounted...

Reviews: