Fig. 22: Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls, with Tankless Heater
Fig. 21: Wiring Diagram for Water Boilers with Beckett AFG Burner and Controls, without Tankless Heater
SEQUENCE OF OPERATION
A call for heat by the thermostat energizes the L8148A control which in turn energizes the R4184D primary control to turn on the
burner. If burner ignites within approximately 45 seconds and the cad cell sees flame, the burner will continue to operate until the call
for heat is satisfied or the setting of the high limit is reached. The circulator will operate as long as the thermostat is calling for heat. If
the thermostat is not satisfied and the high limit is reached, the circulator will continue to operate, and the burner will stop until the high
limit is closed by a drop in boiler water temperature.
SEQUENCE OF OPERATION
A call for heat by the thermostat energizes the L8124C control which in turn energizes the R4184D primary control to turn on the
burner. If burner ignites within approximately 45 seconds and the cad cell sees flame the burner will continue to operate until the call
for heat is satisfied. The circulator will also operate when the thermostat calls for heat if the boiler water temperature is up to the setting
of the low limit in the L8124C control. If boiler water temperature is below the low limit setting the burner will operate but the circulator
will not, giving preference to the domestic hot water demand.
On call for heat by the thermostat the burner will continue to operate until the thermostat is satisfied or the setting of the high limit is
reached. If the thermostat is not satisfied when the high limit is reached the burner will stop but the circulator will continue to operate
until the thermostat is satisfied. Any time the boiler water temperature drops below the setting of the low limit the burner will be
energized in order to maintain domestic water temperature.
Summary of Contents for V7 SERIES
Page 32: ...32 BARE BOILER ASSEMBLY...
Page 34: ...34 BARE BOILER ASSEMBLY CONTINUED...
Page 36: ...36 TS 39 112 D V713 and V714 FLUSH JACKET...
Page 38: ...38 V72 Thru V79 FLUSH JACKET TS 39 109 D...
Page 40: ...40 V73 Thru V79 STEAM BOILERS TRIM AND CONTROLS...
Page 42: ...42 V72 Thru V79 V713 and V714 WATER BOILERS TRIM AND CONTROLS...
Page 44: ...44 Beckett AFG Burner...
Page 46: ...46 Print word document...
Page 47: ...47...