2.
INTRODUCTION
Thank you for choosing this burley product. All of our products carry a CE mark which is awarded by
an independent test house (notified body) and shows the fires have been type tested to meet the
essential requirements of the European Gas Appliance Directive and the appropriate British
Standards.
This is a highly efficient Flueless Inset Live Fuel Effect Appliance. The burner system is very clean
burning and a catalyst cleans the combustion products even further.
A thermostat in the burner control system adjusts heat output to maintain a room temperature,
which can easily be set by the user. The appliance is operated via a battery powered remote control
system. Operation is also possible on the appliance with push button controls. There is also a
separate control to adjust the flame effect as required. Please demonstrate its operation to the
customer before leaving.
An oxygen depletion sensing pilot light is also fitted and will sense any significant oxygen depletion
in the room and shut the fire down safely.
1.
APPLIANCE DATA
Refer to the appliance data badge (this is located beside the control knob)
ENSURE THAT THE
LOCAL CONDITIONS OF USE CORRESPOND TO THE INFORMATION ON THE DATA BADGE.
Natural Gas G20
LPG (Propane) G31
Category
I2H
I3P
Supply Pressure
20mBar
37mBar
Inlet Pressure
20mBar
37mBar
Heat Input (Net)
(High)
2.5kW
2.5kW (180g/h)
(Low)
1.5kW
1.5kW (107g/h)
Inlet Connection
8mm Compression
8mm Compression
Injector
Elbow 300
Elbow 90
2.
GENERAL REQUIREMENTS
1.
Gas appliances must be installed in accordance with the rules in force. In the UK it is the law
that all gas appliances must be installed by a Gas Safe™ registered installer (formerly
CORGI), in accordance with the Gas Safety (Installation and Use) Regulations (as amended).
The installation must be in accordance with the relevant parts of local and national building
regulations.
For the Republic of Ireland, reference should be made to IS813, ICP3, and guidance from
Bord Gais, building regulations and any other rules in force.
Failure to have the fire fitted by a qualified person nullifies ALL guarantees.
2.
The area in which the fire is installed must have at least 100cm2 of permanent purpose
provided ventilation. For Republic of Ireland, 2 vents of not less than 60cm2 must be
provided at high and low level, with minimum vertical separation of 1.6m. Note wherever
possible, to prevent draughts, these should be on the same wall.
There must be a minimum of 1 metre distance between the fire and any air vent.
Curtains must not obscure air vents.
Floor vents, window vents and chimneys are NOT suitable forms of ventilation. Any
purpose provided ventilation should be checked regularly to ensure it is free from
obstruction