Electrical installation, büS
15
ELECTRICAL INSTALLATION, BÜS
Pin
Wire colour
Assignment
1
2
3
4
5
1
CAN label/shielding
CAN label/shielding
2
red
24 V DC ±25% max. residual ripple 10%
3
black
GND/CAN_GND
4
white
CAN_H
5
blue
CAN_L
Table 41:
Pin assignment
For electrical installation with büS network note the following:
Use a 5-pin circular plug and a shielded 5-wire cable.
The shielding is capacitively connected to the functional earth through the device.
15.1
Connection assignment for external position sensor
(only for remote variant)
4
2
1
3
Fig. 37:
Pin assignment socket, 4-pin
Pin
Assignment
Device end
External circuit/signal level
1
Sensor
S +
+
Remote
sensor
Type 8798
25)
2
Sensor supply –
S –
–
3
Serial interface, A-line
A
A-line
4
Serial interface; B-line
B
B-line
25) For assignment of wire colour see “Table 43”.
Table 42:
Pin assignment; external position sensor
Positioner
pin
Wire colour
Remote sensor with cable type 1
Wire colour
Remote sensor with cable type 2
1
brown
brown
2
white
black
3
green
red
4
yellow
orange
Table 43:
Assignment of wire colour on the remote sensor