67
Electrical installation without fieldbus communication
13.2.4
Pin assignment for operating voltage
Pin
Wire colour*
Assignment
External circuit/signal level
3
green
GND
3
4
24 V DC ±25%
max. residual ripple 10%
4
yellow
+24 V
* The specified wire colours refer to the connection cable available as an accessory with ID No. 919061.
Table 30:
Pin assignment, operating voltage
13.3
Electrical installation with cable gland
13.3.1
Designation of screw-type terminals
11 +
12 –
81
82
31 +
32 –
A
B
+
–
+24 V
GND
Remot
e sensor
Fig. 34:
Designation of screw-type terminals
13.3.2
Connection of terminals
→
Unscrew the four screws on the housing cover and remove the cover.
The screw-type terminals are now accessible.
→
Connect terminals according to the assignment.