Start-up
Button 2
Button 1
Status LED
Fig. 13: Starting X.TUNE
→
Screw off the transparent cap of the positioner to operate the
buttons.
→
Start the
X.TUNE
by pressing button 1
7)
for 5 s.
The device is in the NAMUR state function check, status LED lights
orange.
If the X.TUNE is successfully completed, the NAMUR state is reset
again. The changes are automatically transferred to the memory
(EEPROM) provided the
X.TUNE
function is successful.
When status LED lights red after X.TUNE:
→
Execute X.TUNE again.
→
Perform a device restart if necessary.
The changes are automatically transferred to the memory (EEPROM)
provided the
X.TUNE
function is successful.
7) The X.TUNE can also be started via communications software.
ATTENTION!
Breakage of the pneumatic connection pieces due to rota-
tional impact.
▶
When unscrewing and screwing in the transparent cap, do not
hold the actuator of the process valve but the basic housing.
Damage or malfunction due to penetration of dirt and
humidity.
▶
To observe degree of protection IP65 / IP67, screw the trans-
parent cap in all the way.
→
Close the device (assembly tool: 674078
8)
).
10.3 Setting with Bürkert Communicator
The Bürkert Communicator can be used to make all settings on
the device.
The settings in the Bürkert Communicator can be found in
the operating manual.
8)