![Burkert 8696 REV.2 Quick Start Manual Download Page 11](http://html1.mh-extra.com/html/burkert-0/8696-rev-2/8696-rev-2_quick-start-manual_2832378011.webp)
11
Technical data
6.8
Electrical data
WARNING!
Only circuits with limited power may be used for UL approved
components according to “NEC Class 2”.
6.8.1
Electrical data, without fieldbus
communication
Protection class
III as per DIN EN 61140 (VDE 0140-1)
Connections
Circular plug-in connector
(M12 x 1, 8-pin)
Operating voltage
24 V DC ± 25%,
max. residual ripple 10 %
Current consumption
max. 150 mA
Power consumption
max. 3.5 W
Input resistance for
set-point value signal
75 Ω at 0/4 – 20 mA / 12 bit resolution
Analogue position
feedback max. load
for current output
0/4 – 20 mA
560 Ω
Digital input
0 – 5 V = log “0”, 12 – 30 V = log “1”
inverted input in reverse order
Communications
interface
Connection to PC
via USB-büS interface set
Communication
software
Bürkert Communicator
6.8.2
Electrical data, IO-Link
Protection class
III as per DIN EN 61140 (VDE 0140-1)
Connection
Circular plug-in connector M12 x 1,
5-pin, A-coded, Port Class B
Operating voltage
System supply
(Pin 1+3)
24 V DC ±25 %
(according to specification)
Actuator supply
(Pin 2+5)
1)
24 V DC ±25 %
(according to specification)
Current consumption
System supply
(Pin 1+3)
max. 50 mA
Actuator supply
(Pin 2+5)
max. 100 mA
Total
power consumption
max. 3.5 W
3) Actuator supply is galvanically isolated from system supply in accor-
dance with IEC 60664 and for electrical safety in accordance with
SELV from IEC 61010-2-201
english
Type 8696 REV.2
Summary of Contents for 8696 REV.2
Page 29: ......
Page 30: ...www burkert com ...