48
Start-up
10.7
AS-Interface
AS-Interface (Actuator Sensor Interface) is a field bus system which is used primarily for networking binary
sensors and actuators (slaves) with a higher-level control (master). The unshielded two-wire line is used to
transmit both the information (data) and the energy to supply the actuators and sensors.
10.7.1
Certification
The device is certified according to AS-Interface specification version 3.0.
Certificate No.: on request
10.7.2 Programming data
I/O-Konfiguration
B hex
ID code
A hex (bit configuration see above)
Extended ID code 1
7 hex
Extended ID code 2
E hex
Profile
S-B.A.E
Table 11:
Programming data
Bit configuration
Data bit
D3
D2
D1
D0
Input
0 End position
not reached when
actuator activated
1 End position
reached when
actuator activated
0 End position
not reached when
actuator deacti-
vated
1 End position
reached when
actuator
deactivated
–
–
Output
–
–
“1
→
0” (falling edge)
START automatic
teach function
0 Pilot valve OFF
1 Pilot valve ON
Parameter bit
P3
P2
P1
P0
Output
not used
not used
not used
"1
→
0" (falling
edge)
START automatic
teach function
Table 12:
Bit configuration
english
Type 8695 REV.3