Start-up
Description of workflow for automatic teach function:
The status insicator flashes orange when the teach function is running.
•
The first end position (POS1 = pilot valve deactivated) is scanned in.
•
The pilot valve switches.
•
The actuator moves automatically to the second end position (POS2 = pilot valve activated).
•
The second end position (POS2 = pilot valve activated) is scanned in.
•
The pilot valve is switched off.
•
The actuator moves to the first end position (POS1 = pilot valve deactivated).
10.2.2 Manual teach function
For devices without pilot valve:
The end positions are captured and saved manually by the user.
With the IO-Link and AS-Interface variant, the teach function can also be started via the bus com-
munication (see respective parameter list) or with all variants of the REV.3 versions with the Bürkert
Communicator.
Essential requirements:
•
The device is mounted on the actuator.
•
The supply voltage is connected.
•
The compressed air supply is connected.
•
So that the correct reference conditions are identified, the pilot pressure must correspond to the operating
conditions.
•
Provide the possibility for the user to switch the pneumatic actuator (open and closed).
Body casing
Basic housing
Actuator
Transparent cap
Figure 30:
Opening or closing the device
ATTENTION
Breakage of the pneumatic connection pieces due to rotational impact.
▶
When opening or closing the device, do not press against the actuator, but against the basic housing.
→
Screw off the transparent cap by turning counterclockwise.