21
Electrical connection
Type 8653
8
elecTrical cOnnecTiOn
Caution
risk of injury from electric shock.
►
Before working on the device or system, switch off the power supply. Secure against reactivation.
►
Observe applicable accident prevention and safety regulations for electrical equipment.
risk of injury due to incorrect electrical connection work.
►
The electrical connection work should be carried out by fully trained personnel only.
►
Use suitable tools to establish the electrical connection.
Further information on cabling büS networks can be found under the following link:
Guide for planning of büS networks
note
To ensure electromagnetic compatibility (EMC):
►
Only use shielded cables.
►
Connect the functional earth (see chapter
).
Assignment of circular plug M12, 5-pole, A-coded
View of pins
pin
Assignment
4
5
2
1
3
1
Shielding
2
Supply voltage 24 V
3
GND
4
CAN_H (büS connection)
5
CAN_L (büS connection)
Table 1:
Assignment of circular plug M12, 5-pole
english