english
Type 1094
18
4.2.2 Setting the DIP Switches for the 1094 PHR type
4.2
Setting up the electronics
4.2.1 DIP-switches
Select the PWM frequency and the desired standard signal input (only applies to the
standard rail electronics Type 1094-PHR) corresponding to the listed valve types.
The standard signal input must be determined before connecting
the operating voltage.
NOTE
DIP-Switch
Standard Signal Input
0 - 10 V
0 - 20 mA
4 - 20 mA
S 1-1
OFF
ON
ON
S 1-2
OFF
ON
ON
S 1-3
ON
ON
OFF
S 1-4
ON
ON
OFF
S 1-5
OFF
OFF
ON
PWM-Frequency
DIP-Switch
low
high
S 1-6
OFF
ON
OFF
ON
S 1-7
OFF
OFF
ON
ON
suitable for
2834, 2836
2832, 2834
2832
2821
valve type
6023
6022, 6023
6022, 6023
6021
6223
Zero-point switch-off
DIP-Switch
aktivated
de-aktivated
S 1-8
OFF
ON
Setting at delivery