SpaceKeeper Console (SKC) – Installation Operation Maintenance Manual 
 

         

© Copyright 2013 CGC Group Inc.         Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15, 2019 

 

controls are powered down for at least 20 seconds, and the green power light 
goes out. A soft lockout is a compressor shutdown that will be restored once the 
condition causing the shutdown returns to normal.) 

d.

 

During compressor operation, refrigerant temperature, system fluid 
temperature and discharge air temperature are continuously monitored. If the 
refrigerant temperature drops below 35

F, compressor operation will be 

disabled. After 10 minutes an auto reset occurs and the compressor will be 
enabled as soon as the temperature rises above 60

F. Actual compressor restart 

will be delayed a minimum of 5 minutes by the anti-recycle timer. A flash code 
of 2 will be initiated on LED 15 upon a low refrigerant temperature shutdown. 

e.

 

If during compressor operation the condenser leaving temperature rises above 
140

F, compressor operation will be disabled. After 10 minutes an auto reset 

occurs and the compressor will be enabled as soon as the temperature drops 
below 120

F. The outgoing system fluid sensor is mounted on the leaving fluid 

pipe. Actual compressor restart will be delayed a minimum of 5 minutes by the 
anti-recycle timer. A flash code of 3 will be initiated on LED 15 upon a high 
outgoing system fluid temperature shutdown. 

f.

 

If the discharge air temperature drops below 40

F, compressor operation will 

be disabled. After 10 minutes an auto reset occurs and the compressor will be 
enabled as soon as the temperature rises above 55

F. The discharge air 

temperature sensor is mounted on the fan housing. Actual compressor restart 
will be delayed a minimum of 5 minutes by the anti-recycle timer. A flash code 
of 4 will be initiated on LED 15 upon a low discharge air temperature shutdown. 

g.

 

The condensate level sensor is a 100 ohm thermistor that is heated for 15 
seconds every 4 minutes. Its temperature is measured at the beginning of the 
heat cycle, and again at the end of the heating cycle. If the condensate level 
rises above the sensor it will not warm up during the warm up cycle, and the 
temperature change will be insignificant. It is this lack of temperature change 
that the controller sees as an impending condensate overflow. When high 
condensate level is detected, compressor operation is immediately terminated, 
and at the same time the fan is stopped for 30 seconds, and then restarted. At 
this time a flash code of 7 will be initiated on LED 15. The 4 minute cycle will 
continue until the cooling call is no longer in place. If the condensate level drops 
below the sensor, compressor operation will be returned to normal. However, if 
the condensate level stays above the sensor for more than 15 minutes, the fault 
alarm will be triggered. This fault signal will automatically reset once the 
condensate level goes below the sensor. 

 
Note: The last flash code will be maintained in memory for 1 week or until the unit controls are 
powered down. The flash code will continue until the problem has cleared and the compressor has 

Summary of Contents for SKC008

Page 1: ...llation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 25 2013 Installation Operation Maintenance SpaceKeeper Console BULLDOG Heat Pump SpaceKeeper Console Models SK...

Page 2: ...nts INFORMATION 3 HANDLING 3 STORAGE 3 WEIGHT DIMENSIONS CLEARANCE 4 INSTALLATION 5 DELIVERY AND GENERAL INSTALLATION CHECKLIST 5 ELECTRICAL WIRING 11 OPERATION 12 CAUTION 12 FAN OPERATION 14 HEATING...

Page 3: ...on corrosive environment sheltered from conditions of extreme temperature or humidity Subjecting the unit to conditions of this nature may result in significantly reduced performance reliability and o...

Page 4: ...012 015 018 R410A Charge oz 27 27 30 35 45 Weight Dimensions Clearances Weight Dimensions Model 008 010 012 015 Weight lb 160 160 165 175 Dimensions W X H X D 48 X 25 8 1 X 12 8 3 Dimensions with sta...

Page 5: ...F 29 C to 120 F 49 C Installation Procedure 1 This heat pump unit is to be installed within an indoor environment Locate the unit in an area where the surrounding air temperature is above 45 F 7 C at...

Page 6: ...he black mounting base with the front panel removed 10 With the front panel cover removed locate the three fluid hoses that are attached to the unit s supply return and condensate connections Carefull...

Page 7: ...nce Manual 7 Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 15 Re attach the heat pump unit s cabinet cover and fro...

Page 8: ...Console SKC Installation Operation Maintenance Manual 8 INSTALLATION Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 201...

Page 9: ...ceKeeper Console SKC Installation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 Drawi...

Page 10: ...aceKeeper Console SKC Installation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 Draw...

Page 11: ...ctrical box and receptacle supplied by others to be mounted and wired to the Piping and Receptacle Plate if supplied or mounted within reach of the console unit s power cord Receptacles required to ma...

Page 12: ...extensive unit clean up and void warranty do not operate units without air filters in place and do not operate units during the construction process The BULLDOG Heat Pump provides year round cooling...

Page 13: ...cators located near the input locations which are lit when the input is closed The inputs include High Pressure Switch Low Pressure Switch Heat Call W on thermostat terminal Cool Call Y on thermostat...

Page 14: ...ted LED indicators HEATING OPERATION 1 A call on W for heat will activate the fan at low speed It will also simultaneously energize the heat relay K2 and its associated LED The relay K2 will provide 2...

Page 15: ...algorithm b If the suction pressure drops below the set point of the low pressure switch the switch will open and if it remains open beyond the 5 minute ignore period after start up compressor operat...

Page 16: ...ture drops below 40 F compressor operation will be disabled After 10 minutes an auto reset occurs and the compressor will be enabled as soon as the temperature rises above 55 F The discharge air tempe...

Page 17: ...ERMOSTAT CONNECTIONS The CGC control board has been designed to operate with most standard 24V AC thermostats These are powered from the CGC board with 24V AC and simply switch power ON to each of the...

Page 18: ...b Global night setback c Heating only mode during emergency power periods The CGC controller is also set up so these shutdown functions can be initiated individually with on board 24V power This capab...

Page 19: ...extend the life of the hoses heat exchangers and other water side accessories Water Flow Rate Open all isolation valves to the unit Ensure that the entering and leaving fluid temperatures of the BULLD...

Page 20: ...areas around the electrical wiring and the circuit board Do not adjust or remove any board connections or wiring connections to other components without first powering down the unit Disconnects are u...

Page 21: ...attention to hose assemblies Note any signs of deterioration or cracking and repair leaks immediately Amperage Check on compressor and fan motor Current draw on this equipment should not exceed norma...

Page 22: ...er Console SKC Installation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 STANDARD WI...

Page 23: ...ght 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 DETAILS Dimensional Diagram Piping and Receptacle Plate Note The fresh air...

Page 24: ...llation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 SpaceKeeper Console Hose Assemb...

Reviews: