SpaceKeeper Console (SKC) – Installation Operation Maintenance Manual 
 

         

© Copyright 2013 CGC Group Inc.         Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15, 2019 

 

Ta, Tr, And Tw are 10k Ohm NTP thermistors, while Co is a 100 Ohm NPT thermistor. These 
Inputs do not have LED indicators. 

FAN OPERATION 

 

1.

 

A call on “G” for fan on the thermostat terminal strip will cause the fan to operate 
continuously on low fan speed through K5 on multi speed units. 

2.

 

A call on “W” for heat on the thermostat terminal strip will also cause the fan to 
operate on low speed. If the heating call is still present after a 10 minute period, the 
multi speed units will switch the fan to high speed through Relay K6. 

3.

 

A call on “Y” for cooling on the thermostat terminal strip will cause the fan on multi-
speed units to immediately step up to high speed through Relay K6. 

4.

 

Fan operation will terminate whenever all calls are dropped. 

5.

 

When the fan is operating at high speed, both relays are energized along with their 
associated LED indicators. 

 

 

 

 

HEATING OPERATION 

 

1.

 

A call on “W” for heat will activate the fan at low speed. It will also simultaneously 

energize the heat relay K2 and its associated LED. The relay K2 will provide 24V AC fused 
power directly to the heat valve.  

 

COOL START UP 

 

1.

 

A call on “Y” for cooling initiates a series of checks prior to the start up of the 
compressor. These checks include: 

a.

 

Power ON timer – Compressor operation is delayed for approximately 5 minutes 
after restoration of power. This prevents all units from coming on line at the 
same time when power is restored.  It also prevents compressor jolting with 
intermittent power. 

b.

 

Anti-Recycle timer – There is a 5-minute anti-recycle delay timer that allows the 
refrigeration cycle to achieve pressure equalization so that the compressor is 
unloaded upon start up. 

c.

 

High Pressure Switch – The high refrigerant pressure switch must be closed prior 
to start. LED 11 will be ON.  

d.

 

Low Pressure Switch – The low pressure switch operates primarily as a loss of 
charge protector. It must be closed for compressor start up and its LED 12 will 
be ON. The pressure switch has a 5 minute time ignore subsequent to start-up. 
In some situations, particularly when the unit is cold, the pressure switch will 

Summary of Contents for SKC008

Page 1: ...llation Operation Maintenance Manual is Subject to Change without Notice Last Revised Oct 25 2013 Installation Operation Maintenance SpaceKeeper Console BULLDOG Heat Pump SpaceKeeper Console Models SK...

Page 2: ...nts INFORMATION 3 HANDLING 3 STORAGE 3 WEIGHT DIMENSIONS CLEARANCE 4 INSTALLATION 5 DELIVERY AND GENERAL INSTALLATION CHECKLIST 5 ELECTRICAL WIRING 11 OPERATION 12 CAUTION 12 FAN OPERATION 14 HEATING...

Page 3: ...on corrosive environment sheltered from conditions of extreme temperature or humidity Subjecting the unit to conditions of this nature may result in significantly reduced performance reliability and o...

Page 4: ...012 015 018 R410A Charge oz 27 27 30 35 45 Weight Dimensions Clearances Weight Dimensions Model 008 010 012 015 Weight lb 160 160 165 175 Dimensions W X H X D 48 X 25 8 1 X 12 8 3 Dimensions with sta...

Page 5: ...F 29 C to 120 F 49 C Installation Procedure 1 This heat pump unit is to be installed within an indoor environment Locate the unit in an area where the surrounding air temperature is above 45 F 7 C at...

Page 6: ...he black mounting base with the front panel removed 10 With the front panel cover removed locate the three fluid hoses that are attached to the unit s supply return and condensate connections Carefull...

Page 7: ...nce Manual 7 Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 15 Re attach the heat pump unit s cabinet cover and fro...

Page 8: ...Console SKC Installation Operation Maintenance Manual 8 INSTALLATION Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 201...

Page 9: ...ceKeeper Console SKC Installation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 Drawi...

Page 10: ...aceKeeper Console SKC Installation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 Draw...

Page 11: ...ctrical box and receptacle supplied by others to be mounted and wired to the Piping and Receptacle Plate if supplied or mounted within reach of the console unit s power cord Receptacles required to ma...

Page 12: ...extensive unit clean up and void warranty do not operate units without air filters in place and do not operate units during the construction process The BULLDOG Heat Pump provides year round cooling...

Page 13: ...cators located near the input locations which are lit when the input is closed The inputs include High Pressure Switch Low Pressure Switch Heat Call W on thermostat terminal Cool Call Y on thermostat...

Page 14: ...ted LED indicators HEATING OPERATION 1 A call on W for heat will activate the fan at low speed It will also simultaneously energize the heat relay K2 and its associated LED The relay K2 will provide 2...

Page 15: ...algorithm b If the suction pressure drops below the set point of the low pressure switch the switch will open and if it remains open beyond the 5 minute ignore period after start up compressor operat...

Page 16: ...ture drops below 40 F compressor operation will be disabled After 10 minutes an auto reset occurs and the compressor will be enabled as soon as the temperature rises above 55 F The discharge air tempe...

Page 17: ...ERMOSTAT CONNECTIONS The CGC control board has been designed to operate with most standard 24V AC thermostats These are powered from the CGC board with 24V AC and simply switch power ON to each of the...

Page 18: ...b Global night setback c Heating only mode during emergency power periods The CGC controller is also set up so these shutdown functions can be initiated individually with on board 24V power This capab...

Page 19: ...extend the life of the hoses heat exchangers and other water side accessories Water Flow Rate Open all isolation valves to the unit Ensure that the entering and leaving fluid temperatures of the BULLD...

Page 20: ...areas around the electrical wiring and the circuit board Do not adjust or remove any board connections or wiring connections to other components without first powering down the unit Disconnects are u...

Page 21: ...attention to hose assemblies Note any signs of deterioration or cracking and repair leaks immediately Amperage Check on compressor and fan motor Current draw on this equipment should not exceed norma...

Page 22: ...er Console SKC Installation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 STANDARD WI...

Page 23: ...ght 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 DETAILS Dimensional Diagram Piping and Receptacle Plate Note The fresh air...

Page 24: ...llation Operation Maintenance Manual Copyright 2013 CGC Group Inc Installation Operation Maintenance Manual is Subject to Change without Notice Last Revised Nov 15 2019 SpaceKeeper Console Hose Assemb...

Reviews: