TC-Standard (+) X2
9 Appendices
9.1 Gas cooler technical data
TC-Standard X2
Gas Cooler Technical Data
Ready for operation
after max. 10 minutes
Ambient temperature
5 °C to 50 °C
Gas outlet dew temperature
preset:
adjustable:
5 °C
2 °C…20 °C or Delta T-control
Protection class
IP 20
Mechanical load
Tested to DNVGL-CG-0339, Table 6
2 Hz-13.2 Hz Amplitude ± 1.0 mm
13.2 Hz -100 Hz acceleration
Housing
Stainless steel, brushed
Packaging dimensions
approx. 355 x 220 x 205 mm
Weight incl. heat exchanger
approx. 7.5 kg
approx. 6 kg (for 24 V DC)
approx. 9 kg fully upgraded
Electrical data
Unit without add-on
Unit with add-on
(1 peristaltic pump)
24 V DC
230 V AC
115 V AC
24 V DC
230 V AC
115 V AC
5 A
0.6 A
1.2 A
5.5 A
0.7 A
1.4 A
120 W
110 W / 140 VA
130 W
130 W / 160 VA
Recommended fuse
(characteristic: delayed action)
6,3 A
1,25 A
2,5 A
6,3 A
1,25 A
2,5 A
Status output switching capacity
max. 250 V AC, 150 V DC
2 A, 50 VA, potential-free
Electrical connections
Plug per EN 175301-803
Gas connections and condensate outlet
Heat exchanger see table "Heat Exchanger Overview"
Filter, moisture detector adapter G1/4 or NPT 1/4"
Parts in contact with mediums
Filter:
Moisture detector:
Heat exchanger:
Peristaltic pump:
Tubing:
see "Technical Data - Options"
see "Technical Data - Options"
see table "Heat Exchanger Overview"
see "Technical Data - Options"
PTFE/Viton
Markings:
FM18ATEX0012X: II 3 G Ex ec nC IIC T4 Gc
IECEx FMG 18.0005X: Ex ec nC IIC T4 Gc
FM18US0021X/FM18CA0010X: CL I DIV 2 GP ABCD
34
Bühler Technologies GmbH
BE440023 ◦ 10/2018