TC-Standard (+) X2
5.4.3.1 Submenu 2 (Analog Output 1)
The analog output will display the actual cooler temperature.
Signal behaviour
In normal mode (
noP
) the measuring point will output the actual temperature. For testing purposes you can generate constant
values
hi
,
Lo
or
hALF
. The analogue output will output a constant signal with a value as specified in the table.
Constant
Current output
4 – 20 mA
Voltage output
2 – 10 V
hi
20 mA
10 V
Mi
12 mA
6 V
Lo
4 mA
2 V
noP
4 – 20 mA
2 – 10 V
After testing, the signal behaviour must be changed back to normal mode (
noP
).
Display →
toP
→
An1
→
cout
This setting determines how the analogue output will behave.
Parameter range:
noP
= Operation (normal mode),
hi
,
Lo
,
hALF
Factory setting:
noP
Note:
This menu will be hidden if the menu is locked.
Selection -> Output Signal
Display →
toP
→
An1
→
out
Select the type of output signal.
Parameter range:
i
Status output 4… 20 mA
u
Status output 2…10 V
Factory setting:
i
Note:
Disconnect meter before switching!
This menu item is hidden if the keylock is enabled.
Exit Submenu 2
Display →
toP
→
An1
→
E
Selecting this will return you to submenu 1.
5.4.4 Set favourite menu
Use the
F
or
Func
(function) key to set a favourite menu to later open it with just the push of a button.
– Open the menu you wish to set as the favourite. This menu can also be a lockable menu.
– Press the function key for more than 3 sec.
The current menu has been set as the favourite. The display will briefly show the message
Func
.
– Press
ESC
or
E
(Exit) to return to the display.
To now access the favourite menu, press the
F
or
Func
key.
NOTICE! The favourite menu can also be accessed if the menu is locked.