E-2
English
1.3
1 Please Read
Immediately
1.1 Important Information:
ATTENTION!
The device is not suitable for operation with a frequency converter.
ATTENTION!
When transporting the heat pump, ensure that it is not tilted more than
45° (in any direction).
ATTENTION!
The heat pump and the wooden pallet are only joined by the packing film.
ATTENTION!
Do not restrict or block the area around the air intake or outlet.
ATTENTION!
In the case of large-volume heating circuits, an additional expansion
vessel must be used to supplement the installed expansion vessel (24
litres, 1.0 bar admission pressure).
ATTENTION!
Ensure that there is a clockwise rotating field: Operating the compressor
in the wrong rotational direction could cause damage to the compressor.
ATTENTION!
Never use cleaning agents containing sand, soda, acid or chloride as
these can damage the surfaces.
ATTENTION!
We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump.
ATTENTION!
Before opening the device, ensure that all circuits are isolated from the
power supply.
ATTENTION!
Work on the heat pump may only be carried out by authorised and
qualified after-sales service technicians.
1.2 Legal Regulations and
Directives
The construction and design of the heat pump complies with all
relevant EU directives, DIN/VDE regulations (see CE declaration
of conformity).
When connecting the heat pump to the power supply, the rele-
vant VDE, EN and IEC standards are to be fulfilled. Any further
connection requirements stipulated by local utility companies
must also be observed.
When connecting the heating system, all applicable regulations
must also be adhered to.
1.3 Energy-Efficient Use of the
Heat Pump
With the purchase of this heat pump you are helping to protect
the environment. A prerequisite for energy-efficient operation is
the correct design of the heat source system and heating system
(radiators and circulation pump).
It is particularly important for the efficiency of a heat pump to
keep the temperature difference between heating water and heat
source as small as possible. For this reason, it is advisable to de-
sign the heat source and heating system very carefully.
A tem-
perature difference of approx. one Kelvin (1 °C) increases
the power consumption by around 2.5 %.
When designing the
heating system, it should be borne in mind that special consum-
ers such as e.g. hot water preparation should also be considered
and dimensioned for low temperatures.
Underfloor heating
systems (panel heating)
are optimally suited for heat pump use
on account of the low flow temperatures (30 °C to 40 °C).
It is important to ensure that the heat exchangers are not con-
taminated during operation because this increases the tempera-
ture difference, in turn reducing the COP.
Correct adjustment of the heat pump controller is also important
for energy-efficient use of the heat pump. Further information can
be found in the heat pump controller's operating instructions.
The heat pump is equipped with an
overflow mechanism
to pre-
vent very low flow rates in the heat pump.
The installed buffer tank increases the amount of water in the
heating circuit and guarantees reliable defrosting.
Summary of Contents for WPL 60I
Page 2: ......