Instructions for High Altitude Conversion

8

We reserve the right to make any changes due to technical modifications!

Instructions for high altitude conversion for sealed combustion gas boiler GA124 • Issue 

03/2005

Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de

4

Operating Instructions

STOP!

 Read the safety precautions on page 7 of this 

manual.

1.

Wait five (5) minutes to clear out any gas.  Then 
smell for gas, including near the floor.  If you smell 
gas, STOP!  Follow "B" in the safety information on 
page 7.  If you do not smell gas, go to the next step.

2.

Locate the pilot assembly by looking through the 
access viewing port (Fig. 8, 

Item. 1

) on the burner 

front plate.

3.

Turn the gas control knob (Fig. 9, 

Item. 1

counterclockwise to „ON“.

4.

Turn on the electrical power to the appliance.

5.

Set the thermostat to the desired setting to activate 
the boiler.

6.

The ignition control should initiate sparking at the 
pilot.  The pilot should light and then the main 
burners should light.  If the main burners do not light, 
shut off the main gas piping shutoff valve.  Shut off 
all electric power to the appliance and call your 
service technician or gas supplier.

7.

If the main burners light, then the gas fittings, union 
and orifices must be tested for leaks with a soap and 
water solution. If no leaks are found then go to step 
9.  If any leaks are found, turn off gas control knob 
(Fig. 9, 

Item. 1

) clockwise to "OFF".  Turn off all 

electric power to the appliance, set the thermostat to 
lowest setting.

8.

Repair leaks.  Repeat steps 1 through 7.

9.

Check the supply pressure while the boiler is 
running.  Pressure must be between 4.7 and 10.5 
inches WC for natural gas or 11 and 13 inches WC 
for propane gas.  Record supply pressure on the 
boiler start-up procedure.

Fig. 8

Burner tray box

Item. 1:

viewing port

1

Fig. 9

Gas control

Item. 1:

gas control knob (set to position „ON“)

Item. 2:

test port screw for gas supply measurement

Item. 3:

test port screw for manifold pressure measurement

Item. 4:

protective screw for pilot pressure adjustment

Item. 5:

protective screw for manifold pressure adjustment

1

2

3

4

5

Summary of Contents for Logano GA124-17

Page 1: ...nstalled by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction and in accordance with the requ...

Page 2: ...Conversion data plate to be filled out and affixed to the appliance Conversion instructions Technical documents WARNING DANGER Denotes a possible severely dangerous situation where without proper caut...

Page 3: ...3 Remove jacket panel screws Fig 1 Item 1 from left and right side tilt forward top of front jacket panel Fig 1 Item 2 then lift up from the bottom and remove 4 Turn the gas control manual knob Fig 2...

Page 4: ...he flame roll out switch Fig 4 Item 3 10 Remove the burner tray cover plate screws and remove this cover plate Fig 4 Item 4 11 Remove burner tray mounting nuts Fig 4 Item 1 and take entire burner tray...

Page 5: ......

Page 6: ...ter to measure the supply pressure 26 Remove the manifold pressure tapping plug Fig 7 Item 3 from the gas control Install a test fitting and hook up a manometer to measure the manifold pressure 27 Ope...

Page 7: ...ll not turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water...

Page 8: ...and then the main burners should light If the main burners do not light shut off the main gas piping shutoff valve Shut off all electric power to the appliance and call your service technician or gas...

Page 9: ...urner flame Fig 11 Item 1 through the viewing port Fig 8 Item 1 in the burner cover plate The flame should have a smooth firm contour and must be mostly blue in color If the main flame is satisfactory...

Page 10: ...essure tabs in the gas control and replace the plugs 19 Repeat steps 1 to 6 and 13 to place the appliance back in operation Check the plugs in the gas control with a soap and water solution If no leak...

Page 11: ...rve the right to make any changes due to technical modifications Instructions for high altitude conversion for sealed combustion gas boiler GA124 Issue 03 2005 Buderus Heiztechnik GmbH http www heizte...

Page 12: ...3 552 1100 Fax 603 584 1681 www buderus net BBT North America Corporation reserves the right to make changes without notice due to continuing engineering and technological advances Heating Contractor...

Reviews: