Instructions for High Altitude Conversion
3
We reserve the right to make any changes due to technical modifications!
Instructions for high altitude conversion for sealed combustion gas boiler GA124 • Issue
03/2005
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
3
High Altitude Con
v
ersion over
85
00 feet
For your safety, read these instructions before
converting the boiler.
To convert the boiler for use at high altitude, the
following instructions shall be adhered to:
The boiler shall be converted prior to installation.
1.
If the boiler has been in operation, shut off the main
gas valve. If the boiler has not been placed into
service, go to step 3.
2.
Turn off all electric power to the appliance and set
the thermostat to its lowest setting.
3.
Remove jacket panel screws (Fig. 1,
Item. 1
) from
left and right side, tilt forward top of front jacket panel
(Fig. 1,
Item. 2
) then lift up from the bottom and
remove.
4.
Turn the gas control manual knob (Fig. 2,
Item. 1
)
clockwise to the "OFF" position. Do not use
excessive force.
Fig. 1
Removal of front jacket panel
Item. 1:
jacket panel screws
Item. 2:
front jacket panel
1
2
WARNING!
DANGER
When these instructions are not followed.
When the boiler must be converted to
Propane, you should first convert the
boiler from natural gas to propane by
following the Propane Conversion Kit
Instructions. Afterwards convert the
boiler to high altitude.
Fig. 2
Gas control
Item. 1:
gas control knob (set to position „ON“)
1
WARNING!
DANGER
For explosion due to gas.
Wait five (5) minutes to clear out any
gas. Then smell for gas, including near
the floor. If you smell gas, STOP!
Follow "B" instructions in the safety
information printed on page 8. If you do
not smell gas, go to the next step.