Installation and Maintenance Manual Logalux LT135/2 – 300/2 • Issue 05/2003
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Putting the Tank in/out of Operation
7
7.2
Operating Notice
Notify the end-user/owner of the following points:
–
Make sure to always keep P and T relief piping open
and unobstructed (Fig. 13, page 13).
–
Periodically to check the operation of the P and T
valve by manually opening the valve.
–
To contact a qualified service company or contractor
if the manual reset trips regularly on the boiler (if
required by local code).
7.3
Taking out of Operation
In case the tank is not used for a long time, we
recommend the following:
Keep the tank in operation.
Set the control to the vacation function (Logamatic),
or set the tank to its minimum setting.
When the tank has been taken out of operation, observe
local code and regulations regarding placing the tank
back in operation and possibly rinsing the domestic
water lines.
CAUTION!
TANK DAMAGE
When the pressure/temperature relief
valve is blocked or damaged, potential
damage may occur to the tank and a very
dangerous situation can develop.
Make sure that the P and T relief
piping Fig. 13, page 13) is
NEVER
blocked.
NOTICE
Information regarding operation of the
sensor/aquastat can be obtained from the
documentation furnished with the control.
CAUTION!
TANK DAMAGE
When the tank is kept empty for several
days, localized corrosion can take place
due to residual moisture.
Dry out the tank interior using warm air
and keep the access port open.