5
We reserve the right to make technical modifications.
W
• http://www.buderus-commercial.co.uk
Installation instructions Logamax plus GB162-80/100 cascade unit • Version 01/2006
Items supplied with unit
2
Buderus supplies cascade systems in
TL
and
TR
configurations:
TL: Inline installation
All boiler assemblies are in a line enabling an easy-to-monitor
installation in a narrow room.
TR: Back-to-back installation
The boiler assemblies are located on both sides of the frame
and are installed back-to-back to create a compact installation
which ideally suits rectangular rooms and which ensures the
best possible access to all boilers.
The relevant configuration can be selected on the basis of the
performance required (see table 1).
Boiler assembly connection kit
The connection kit can be used both for the Logamax plus
GB162-80 and for the 100-kW version. The connection kit
includes a pressure relief valve, a non-return valve, a pump
and isolating valves.
Bend sets with low loss header
The Logamax plus GB162 cascade system can be installed in
various configurations (fig. 4). By using the bend set the low
loss header can be installed at an angle to the boilers. The gas
pipe is reversible so that the gas connection can be at the other
side of the boilers to the flow and return connections to the
header.
Appliance
performance
[kW]
Cascade
system options
TL = inline
TR = back-to-back
Number of boilers
Logamax plus
GB162
80
100
80
Single installation
1
–
100
Single installation
–
1
160
TL2 or TR2
2
–
180
TL2 or TR2
1
1
200
TL2 or TR2
–
2
240
TL3 or TR3
3
–
260
TL3 or TR3
2
1
280
TL3 or TR3
1
2
300
TL3 or TR3
–
3
340
TL4 or TR4
3
1
360
TL4 or TR4
2
2
380
TL4 or TR4
1
3
400
TL4 or TR4
–
4
440
TL5 or TR5
3
2
460
TL5 or TR5
2
3
480
TL5 or TR5
1
4
500
TL5 or TR5
–
5
520
TL6 or TR6
4
2
540
TL6 or TR6
3
3
560
TL6 or TR6
2
4
580
TL6 or TR6
1
5
600
TL6 or TR6
–
6
620
TL7 or TR7
4
3
640
TL7 or TR7
3
4
660
TL7 or TR7
2
5
680
TL7 or TR7
1
6
700
TL7 or TR7
–
7
720
TL8 or TR8
4
4
740
TL8 or TR8
3
5
760
TL8 or TR8
2
6
780
TL8 or TR8
1
7
800
TL8 or TR8
–
8
Table 1 Cascade selection
Low loss
header
TL- configuration
(inline)
TR- configuration
(back-to-back)
2½"
TL2, TL3
TR2
3"
TL4
TR3, TR4
4"
TL5, TL6, TL7, TL8
TR5, TR6, TR7, TR8
Table 2 Low loss header configuration
Fig. 4
Cascade system configuration varieties
1
2
1
2
1
2
1
2
1
2
1
2